Equipment Specifications; Mechanical Specifications - Watts OneFlow OF1465-50TM Manuel D'installation, D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Equipment Specifications

OneFlow
systems are complete, self-contained, loaded with media,
®
and ready to use. A simple inlet and outlet connection is all that is re-
quired for installation. Please review operating pressures, temperatures
and water chemistry limitations to ensure compatibility.
B
Feed Water Chemistry Requirements
pH
6.5 to 8.5
Hardness (maximum)
75 grains (1282 ppm CaCO3)
Water Pressure
15psi to 100psi (103 kPa to 6.9 bar)
Temperature
40°F to 110°F (5°C to 43°C)
Chlorine
< 2ppm
Iron (maximum)*
0.3 mg/l
Manganese (maximum)* 0.05 mg/l
Copper (maximum)*
1.3 ppm
Oil & H2S
Must be removed prior to OneFlow
Polyphosphate
Must be removed prior to OneFlow
Silica (maximum)
20 ppm
WARNING
!
High levels of Copper will foul OneFlow
=
nates from new Copper plumbing. Wait a minimum of 4 weeks
before placing system in operation. Avoid applying excess flux on
the inner surfaces of the pipe and to use a low-corrosivity water
soluble flux listed under the ASTM B813 standard.
NOTICE
OneFlow
media does not reduce silica scaling. Silica can act
®
== 
as a binder that makes water spots and scale residue outside
the plumbing system difficult to remove. This 20 ppm limita-
tion is for aesthetic purposes.
NOTICE
Water known to have heavy loads of dirt and debris may require pre-
filtration prior to OneFlow
.
®
* See note about iron, manganese and copper on page 2.
Systems using OneFlow
technology prevent hard water scale
®
formation inside the plumbing system at influent hardness levels of 75
grains per gallon of calcium carbonate and less. Due to variances in
water chemistry, certain aesthetic conditions external of the plumbing
system may not be attained.
OneFlow
is designed for the treatment of potable water that meets the
®
requirements of the current USEPA Safe Drinking Water Act.
A
=
==
media and typically origi-
®

Mechanical Specifications

Inlet/Outlet Connection 2" FNPT (for both systems)
MODEL
Dry Weight (lbs / kgs)
Service Weight (lbs / kgs)
Inlet/Outlet Connection
Replacement Media
Model
Replacement Frequency
OF1465RM
Media should be replaced every 3 years
OF1665RM
Media should be replaced every 3 years
Dimensions
(nominal - inches)
MODEL
a
b**
** The overall height and the height of the inlet fitting varies due
to material variations and assembly tolerances. Please allow
additional clearance above the tank for making connections.
Maximum Service Flow (gpm) vs.
Water Temperature
Continuous Duty Systems:
System
40°F
OF1465-50TM
40
OF1665-75TM
45
Intermittent Duty Systems:
OF1465-50TM
OF1665-75TM
®
Intermittent duty is defined as less than 2 hours of Maximum
®
Flow per 24 hour period. Higher Flow rates can be achieved by
combining systems in an array.
Models
OF1465-50TM
OF1665-75TM
*** Exceeding maximum flow can reduce effectiveness and void warranty.
Pressure drop at peak flow rate is less than 10 psi.
Pressure drop reading taken with inlet and outlet gauges installed at a com-
mon elevation and 80 degree feed water.
NOTICE
• We recommend the installation of a dual-union ball-valve on the
inlet and outlet to isolate the tank for servicing.
• A full bypass should be installed so that the full service flow can
be routed around the system as needed for servicing.
• The OneFlow
system operates in the Up-Flow mode which is
®
opposite of a conventional softener. Special attention needs to
be taken to properly plumb system. On top of the head, "Inlet"
and "Outlet" are embossed above the each port.
3
OF1465-50TM
66 / 30
400 / 181
2" FNPT
OF1465-50TM
OF1665-75TM
14
73.1
45°F
50°F
55°F
60°F
44
48
50
50
51
56
59
63
50 GPM at all temperatures
75 GPM at all temperatures
Maximum Flow Rate***
gpm
lpm
50
189
75
284
OF1665-75TM
75 / 34
480 / 218
2" FNPT
16
73.1
65°F
70°F
50
50
69
75