5.3
Installing the circulation pump
If you use a product version without pre-assembled circulation pump, you
must install a suitable circulation pump with a length of 180 mm yourself.
 Verify that you use the seals enclosed with the product.
1. Observe the specifications of the pump manufacturer.
Mounting
6. Install the screws.
- Tightening torque 3 Nm
2. Pull the two centre parts
of the heat insulation to
the sides.
3. Remove the upper part of
the heat insulation.
4. Mount the pump with the
enclosed flat gaskets and
the union nuts G2.
- Connection thread G2,
tightening torque 80 Nm.