ISU Name
ISU Options (defaults in bold)
256
EM Heat Type
Electric, Gas/Oil (or Fossil Forced Air)
260
Fossil Kit Control
Thermostat, External (Fossil Fuel Kit Controls Backup Heat)
300
Auto Changeover
On, Off
Default setting varies depending on manufacture date
303
Auto Differential
0 °F to 5 °F or 0.0 °C to 2.5 °C
Default setting varies depending on manufacture date
305
High Cool Stage
Yes, No
Finish
306
High Heat Stage
Yes, No
Finish
340
Aux Heat Droop
0 = Comfort; 2 °F to 15 °F from setpoint (in 1 °F increments)
or 1.0 °C to 7.5 °C from setpoint (in 0.5 °C increments)
350
Up Stage Timer Aux
Off, 30, 45, 60, 75, 90 minutes
Heat
2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours
355
Balance Point
Off, 5 °F to 60 °F (in 5 °F increments) or 15.0 °C to 15.5 °C
(Compressor
(in 2.5 °C or 3.0 °C increments)
Lockout)
356
Aux Heat Lock Out
Off, 5 °F to 65 °F (in 5 °F increments) or
(Aux Heat Outdoor
-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)
Lockout)
Notes
This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1 AND if ISU 253
is set to run AUX/E heat separately.
This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1, AND if ISU 256
is set to Gas/Oil.
OFF: The user must select heating or cooling as needed to maintain the desired indoor temperature.
ON (Automatic): On (enabled) Allows user to select Auto Changeover as one of the system modes from the
home screen. In auto mode, the thermostat control either heating or cooling automatically to maintain the
desired indoor temperature.
Differential is NOT deadband. Resideo uses an advanced algorithm that fixes deadband at 0 °F. The differential
setting is the minimum number of degrees from set-point needed to switch from the last mode running (heat
or cool) to the opposite mode when the thermostat is in auto-changeover. This is more advanced than previous
thermostats.
This ISU is only displayed when the thermostat is set to 2 cool stages. When set to YES, this feature keeps the
higher stage of the cooling equipment running until the desired setpoint is reached.
This ISU is only displayed when the thermostat is set to 2 or more heat stages. When set to YES, this feature
keeps the higher stage of the heating equipment running until the desired setpoint is reached.
Aux heat droop can be set on heat pump systems with an auxiliary heat stage. The Comfort setting is NOT
available for Dual Fuel systems. Default setting is 0 °F (Comfort) for Electric while 2 °F for Gas/Oil. The indoor
temperature must drop to the selected droop setting before the thermostat will turn Aux Heat on. For example,
if Aux Heat is set to 2 °F (1.0 °C), the indoor temperature must be 2 ° F (1.0 ° C) away from the setpoint before
Aux Heat turns on. When set to Comfort, the thermostat will use Aux Heat as needed to keep the indoor tem-
perature within 1 °F (0.5 ° C) degree of the setpoint.
The Auxiliary Heat Upstage Timer starts when the highest stage of the previous heating equipment type turns
on. Auxiliary heat will be used (if needed) when the timer expires. This ISU is only displayed when ISU 340 (AUX
Heat Droop) is set to 2 °F or higher.
Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to the temperature below
which it is inefficient to run the heat pump. When outside temperature is below this setting, thermostat will
lockout the heat pump and run Aux Heat only. This ISU is only displayed if ISU 130 = Wired, ISU 200 is set to
Heat Pump, ISU 221 Aux/E stages = 1. Default is 40 °F if ISU 205 Heating Equipment is Air to Air Heat Pump
and ISU 255 Aux Heat Type is Gas/Oil. Default is Off if ISU 205 Heating Equipment is Air to Air Heat Pump and
ISU 255 Aux Heat Type is Electric. Default is Off if ISU 205 Heating Equipment is Geothermal. Compressor
Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump).
Aux Heat Lockout requires an outdoor temperature. Set Aux Heat Lockout to optimize energy bills and to not
allow to run the more expensive Aux Heat source above certain outdoor temperature limit. This ISU is only
displayed if ISU 130 = Wired, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1.