Notes on the timer function in conjunction with the ramp function
- Generally, the setpoints can also be approached using the ramp function.
- Stopping the timer does not influence the ramp function.
- If control is active after the timer has run down, the current setpoint is approached with the
ramp. Cancellation of the timer is followed by a setpoint step without ramp.
- For timer functions with a tolerance limit, only the setpoint (=ramp end value) is monitored.
Note on setpoint switching via the logic input
- Setpoint switching via the logic input is generally possible. An exception here is the timer
function "Time-dependent setpoint switching". In this case, configured setpoint switching via
the logic input will not be active.
Note on the display status in the event of a power failure
- The state of the display before the power failure will be restored, except for events that are
related to the timer (start, cancel, continue, stop). Then the timer value will be shown in the
display.