Error Correction - Trotec IDS 100 Mode D'emploi

Masquer les pouces Voir aussi pour IDS 100:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20
Problem
Operation indicator Self-diagnostic
Fan starts running and
continuous green
flame burns with smoke
light
formation
Device does not switch off continuous green
light
B-8
Reset button
Cause
indicator
Solenoid valve defective
continuous orange
Internal error of the elec-
light
tronic control unit
-
insufficient supply of com-
bustion air
Supply of combustion air
too high
used heating oil contami-
nated and/or containing
water
air has entered the heating
oil circuit
insufficient
quantity at the burner
too much heating oil at the
burner
Solenoid valve seal defec-
-
tive
Operating manual – IDS 100

Error correction

Contact the customer service in order to:
- have the electrical connections checked.
- have the safety thermostat LI checked.
- have the solenoid valve cleaned or replaced.
Contact the customer service in order to:
- have the control unit reset; try to start up the de-
vice at least twice. If the fault still occurs after-
wards, replace the control unit.
- Remove all obstacles or blockages from the intake
and/or exhaust openings.
- Have the position of the air setting ring checked by
the customer service.
- Have the support disc of the burner cleaned by the
customer service
- Have the position of the air setting ring checked by
the customer service.
- Replace used heating oil with clean heating oil.
- Clean the heating oil filter.
- Have the tightness of the lines and heating oil filter
checked by the customer service
heating
oil
Contact the customer service in order to:
- have the pump pressure value checked.
- have the nozzle cleaned or replaced.
Contact the customer service in order to:
- have the pump pressure value checked.
- have the nozzle replaced.
- Have the solenoid valve replaced by the customer
service.