Communication
Power supply
Bus cable
Bus current consumption
Command elements
Display elements
Actuation elements
Maximum switchover current
Maximum power for load type
Maximum dissipated power
Ambit of use
Operating temperature
Storage temperature
Relative humidity
Bus connection
Electrical connections
Protection ratings
Dimension
Reference standard
Certifications

TECHNICAL DATA

KNX Bus
via the KNX bus, 29 V dc SELV
KNX TP1
10 mA max
1 miniature programming key
4 push-buttons for local relay command
1 red programming LED
4 green LEDs for signalling output status
4 relays with NO potential free contact
10A (cos =1)
Incandescent lamps (230Vac): 1500W
Halogen lamps (230Vac): 1500W
Loads controlled by electronic transformers: 600VA
Uncompensated fluorescent loads: 400VA
Low consumption lamps
(compact fluorescent lamps): 8x23W
For compensated fluorescent lamps and all other
loads not indicated here, you are advised to use a
support relay
4W
Indoors, dry places
-5 to +45 °C
-25 to +70 °C
Max 93% (non condensative)
Coupling terminal, 2 pin Ø 1 mm
Extractable screw terminals
Max. cable section: 4 mm
IP20
4 DIN modules
Low voltage directive 2006/95/EC
Electromagnetic Compatibility Directive 2004/108/EC
EN50428, EN50090-2-2
KNX/EIB
27