EXD-S.. Stand Alone Driver Modules are for driving ALCO stepper motor
driven electronic expansion valves series EXV-5, -6, -7, -8. These instructions
are for versions supplied after Datecode 2803.
!
Safety instructions:
• Read operating instruction thoroughly. Failure to comply can result in
device failure, system damage or personal injury.
• It is intended for use by persons having the appropriate knowledge and skill.
• Switch off all voltages / currents before cabling.
• Comply with local electrical regulations when wiring
• Do not operate system before all cable connections are completed.
• Do not apply 110/220/230 V to any terminal of driver module
Installation and wiring
• Install EXV in system per operating instructions of valve.
• Make sure that driver type matche to the type of valve and refrigerant in the
system as follows:
Driver module type
EXD-S05
EXD-S06
EXD-S07
EXD-S08
EXD-S15
EXD-S16
EXD-S17
EXD-S18
EXD-S25
EXD-S26
EXD-S27
EXD-S28
EXD-S35 / EXD-S35S
EXD-S36 / EXD-S36S
EXD-S37
EXD-S38
EXD-S45
EXD-S46
• Install Driver Module, pressure transmitter and temperature sensor.
• Set-up all wire connections as shown wiring diagram.
• Recommended wire cross section between 0.5 mm
• Keep sensor cables separate from all other power and driver lines.
Start-up procedure:
• Do not apply voltage to the driver before completion of wiring.
• Do not operate the driver and valve when the system is under vaccum or
without refrigerant except for closing valve before charging of system.
• Vacuum the entire system.
• Warning: Alco EXVs are delivered at half open position. Do not charge
system before closure of valve.
• Apply supply voltage to driver module for the following times without
activation of digital input to terminals ID/Avss of driver module:
Valve
Time, seconds
EX5/EX6
Min: 2
EX7/EX8
Min: 6
• After closure of valve, intrup power supply to driver module and charge the
system with refrigerant.
• Start the system and check the superheat and operating conditions.
Technical data, power supply:
• Main supply voltage: 24V AC (+10%, -15%), 50-60Hz; 24 VDC (+10%, -0%).
Power supply line to driver to be protected by 1.0 A external fuse.
• Use a safety class II transformer. Minimum power required 20VA.
• Emergency supply voltage (from ECP-024): approx. +18 V DC.
Technical data, inputs:
• 1 analogue input 4-20mA for pressure transmitter, measurement range -0.8 to 7
bar (PT4-07S) or 0 to 18 bar (PT4-18S).
• 1 NTC analogue input, very fast responce with precision ±0.5K
• 1 digital input for 5V/5mA insulated contact (potential free/dry contact)
Outputs:
• 4 current-outputs for stepper motor of EX5/EX6/EX7/EX8.
Nominal current: 0.5A for EX5/EX6, 0.75A for EX7 and 0.8A for EX8.
Maximum cable length: 6 meter AWG20/22.
• 1 digital output for alarm relay, rated power 10VA, 0.5A resistive at 24VAC.
Contact normally open. (The contact is closed under normal operating
conditions; it is open under alarm conditions or when there is no power supply).
Number of automatic operating cycles: (relay) 100.000.
• 1 +24VDC supply output for PT4.
Uninterruptible power supply ECP-024
• Power supply voltage: 24 VAC ± 10%
• Power outputs: Two, each +18VDC
Document Nr.: A6.5.070 / 08
ALCO CONTROLS
Tel.: 07151 509-0 - Fax.: -200
alcoservice@ecopeland.com
Valve
Refrigerant
EX5
R22
EX6
R22
EX7
R22
EX8
R22
EX5
R407C
EX6
R407C
EX7
R407C
EX8
R407C
EX5
R134a
EX6
R134a
EX7
R134a
EX8
R134a
EX5
R404A
EX6
R404A
EX7
R404A
EX8
R404A
EX5
R410A
EX6
R410A
2
2
and 2.5 mm
.
Max: 30
Max: 30
Replacement for A6.5.070 / 07
Operating Instructions
Stand Alone Driver Module EXD-S Series
for Electronic Expansion Valves EX5 ... EX8
Indicator and Error Messages
Description
Priority
level
Off
Power supply
Valve is opening
Valve is fully open
Valve is closing
Valve is fully close
EEPROM read err. 1, High
Motor connection
error
Pressure and or
temperature
probe(s) error
EEPROM write error
4, Low
Note: In case where more than one alarm is active, the alarm with higher priority
is displayed.
Wiring Diagram
Digital output
Power
alarm relay
output for
second
driver in
system, if
Valve is opening
available
Valve is closing
*) These terminals are for use with specific
controller and should not be wired.
**) Digital input: The contact should be
wired based on system operation
configuration:
a) Direct start and stop of compressor:
The contact will be activated/deactivated as
the first stage compressor starts or stops.
b) Pump down:
The contact will be activated/deactivated as
cooling demand activated/deactivated. The
compressor will be activated/deactivated by
low pressure switch.
Date: 21.04.2006
Valve opens
Valve closes
green LED
Green LED
-
Off
Off
-
-
-
-
Blink
Off
-
On
Off
-
Off
Blink
-
Off
On
Off
Off
2
Blink
Blink
3
Off
Blink
Off
Off
Electrical
connection plug
EX5-Nxx
GB
Power
Alarm
green LED
red LED
Off
Off
On
Off
On
Off
On
Off
On
Off
On
Off
On
Blink
On
On
On
On
On
On
Power supply
Transformer
Fuse
1.0 A
Electrical
connection
PCN: 862970

Publicité

loading

Sommaire des Matières pour Emerson ALCO CONTROLS EXD-S Serie

  • Page 1 ALCO CONTROLS Operating Instructions Emerson Electric GmbH & Co OHG Stand Alone Driver Module EXD-S Series Heerstr.111 - D 71332 Waiblingen Tel.: 07151 509-0 - Fax.: -200 for Electronic Expansion Valves EX5 … EX8 alcoservice@ecopeland.com www.alco-controls.com – EXD-S.. Stand Alone Driver Modules are for driving ALCO stepper motor driven electronic expansion valves series EXV-5, -6, -7, -8.
  • Page 2: Sicherheitshinweise

    ALCO CONTROLS Betriebsanleitung Emerson Electric GmbH & Co OHG Elektronische Überhitzungsregler EXD-S Heerstr.111 - D 71332 Waiblingen Tel.: 07151 509-0 - Fax.: -200 für elektronische Expansionsventile EX5 … EX8 www.alco-controls.com – alcoservice@ecopeland.com Die elektronischen Überhitzungsregler der Baureihe EXD-S werden zusammen •...
  • Page 3 ALCO CONTROLS Návod k montáži Emerson Electric GmbH Co OHG Řídící modul EXD-S Heerstr. 111 – D 71332 Waiblingen k ventilům EX5 …EX8 www.alco-controls.de; AlcoService@ecopeland.com Samostatný ovládací modul EXD-S pro elektronické krokové expanzní ventily Signalizace poruch a provozních stavů ALCO řady EX5 až EX8 Poruchy (červená) a provoz (zelená) signalizují...
  • Page 4 ALCO CONTROLS Instrukties voor het gebruik Emerson Electric GmbH & Co OHG Elektronische oververhittingsregelaar EXD-S Heerstr.111 - D 71332 Waiblingen voor elektronische expansieventielen EX5..EX8 Tel.: 07151 509-221 - Fax.: -200 De elektronische oververhittingregelaar EXD-S worden tesamen met de normale bedrijfscondities, en is open bij alarm of spanningsuitval). Aantal elektronische expansieventielen EX5, -6, -7, -8 ingezet.
  • Page 5 ALCO CONTROLS Instrucciones de Operación Emerson Electric GmbH & Co OHG Módulo de Control Autónomo Serie EXD-S Heerstr.111 - D 71332 Waiblingen Tel.: 07151 509-0 - Fax.: -200 para Válvulas de Expansión EX5 … EX8 www.alco-controls.com – alcoservice@ecopeland.com Los módulos de la serie EXD-S.. se utilizan para controlar las válvulas de Salidas: expansión electrónicas ALCO de motor paso a paso EXV-5, -6, -7, -8.
  • Page 6 ALCO CONTROLS Instructions de fonctionnement Emerson Electric GmbH & Co Module d’alimentation autonome série EXD-S Heerstr.111 - D 71332 Waiblingen Tel.: 07151 509-0 - Fax.: -200 pour vannes électronique EX5 … EX8 alcoservice@ecopeland.com www.alco-controls.com – fonctionnement normal, il est ouvert lorsque l’alarme est déclenché ou lorsque Les modules pilote autonomes EXD-S.alimentent les vannes de détente...

Ce manuel est également adapté pour:

Alco controls exd-s05Alco controls exd-s06Alco controls exd-s07Alco controls exd-s08Alco controls exd-s15Alco controls exd-s16 ... Afficher tout