Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Sounder - DB3B
English
Ex d & Ex de – DC input, dual stage common
+ve with monitoring (standard configuration)
wiring details (Types 7 & 8)
Connect up to 4 supply wires to the terminals as detailed
in the wiring diagram. Stage 1 is produced when power is
applied across the common +ve and stage 1 -ve terminals.
Stage 2 is produced when power is applied across the
common +ve and stage 2 -ve terminals.
Monitoring functionality is obtained when the supply is
connected across M1 & M2 terminals.
N
ote:
monitored terminals are not polarity dependent.
Ex d & Ex de – DC input, dual stage common +ve
diagram (Types 7 & 8)
DB3B DC DUAL STAGE
COMMON POSITIVE CONFIGURATION
WITH MONITORING
COMMON +VE / M1 IN
STAGE 1 -VE IN
M2 IN
STAGE 2 -VE IN
COMMON +VE / M1 OUT
STAGE 1 -VE OUT
M2 OUT
STAGE 2 -VE OUT
MONITORING FUNCTIONALITY ONLY
AVAILABLE WHEN RESISTOR IS FITTED
COMMON +VE IN
COMMON +VE OUT
STAGE 1 -VE OUT
STAGE 3 -VE OUT
STAGE 2 -VE OUT
4
Sounder - dB3B
Ex d
Ex de
1
1
2
2
3
3
4
4
5
1
6
2
7
3
8
4
DB3B DC TRIPLE STAGE
COMMON POSITIVE
CONFIGURATION
Ex d
1
STAGE 1 -VE IN
2
STAGE 3 -VE IN
3
4
STAGE 2 -VE IN
5
6
7
8
TM264 July 2020 www.eaton.com
Ex d & Ex de – DC input, up to 3 stage with or
without monitoring (alternative configuration)
wiring details (Types 9 & 10)
N
ote:
This alternative configuration must be specified
when ordering the unit.
This type can be connected either as a three stage
common –ve configuration, or if an optional EOL is specified
if can be configured as a dual stage common –ve system
with monitoring.
4-wire system (Triple stage, Common +ve): Connect
4 supply wires to the terminals as detailed in the wiring
diagram (1 common +ve wire and 3 -ve wires). Stage 1
is produced when power is applied across the common
+ve and stage 1 -ve terminals. Stage 2 is produced
when power is applied across the common +ve and
stage 2 -ve terminals. Stage 3 is produced when
power is applied across the common +ve and stage
3 -ve terminals.
4-wire system (Dual stage, common –ve with
monitoring): Connect up to 4 supply wires to the
terminals as detailed in the wiring diagram. Stage 1 is
produced when power is applied across the common
-ve and stage 1 +ve terminals. Stage 2 is produced
when power is applied across the common -ve and
stage 2 +ve terminals.
Monitoring functionality is obtained when the supply is
connected across M1 & M2 terminals.
Note: monitored terminals are not polarity dependent.
Ex d & Ex de – DC input, up to 3 stage diagrams
(Types 9 & 10)
DB3B DC DUAL STAGE
COMMON NEGATIVE CONFIGURATION
Ex de
STAGE 2 +VE IN
1
2
STAGE 1 +VE IN
3
COMMON -VE / M2 IN
4
STAGE 2 +VE OUT
1
2
STAGE 1 +VE OUT
3
COMMON -VE / M2 OUT
4
MONITORING FUNCTIONALITY ONLY
AVAILABLE WHEN RESISTOR IS FITTED
WITH MONITORING
Ex d
Ex de
1
M1 IN
2
3
4
5
M1 OUT
6
7
8
1
2
3
4
1
2
3
4

Publicité

Table des Matières
loading