TEMPERATURE ADJUSTMENT - INSTALLATION WITH LOOP
Example of normal "mixed water" operation WITH RECIRCULATION LOOP
VM1 - VM2 : micrometric valves to stabilise
the recirculation loop temperature
VM1A : open between 70 and 90%
VM1B : open between 30 and 10%
Mixed water T° probe
DHW
production
probe
T
Buffer
Tank
65°C
Primary
7 bar
Symbols
Thermostatic
Cold water
mixing
Mixed water
valve
Hot water
Wired link
Check valve EA
included
(anti pollution)
Optional wired
connection
SETTING MODE
1 - Operate the circulator, and ensure that the temperature of DHW production is
greater than the set value of the loop.
2 -Go to setting mode
3 - Set the desired set temperature by successive press on
then validate by pressing
The e-Ultramix adjusts automatically for up to 5 minutes
(the LED of the actuator starts to flash after 15 s).
Stay on this screen and maintain flow rate for the duration of the adjustment.
The setting ends with memorization by switching to normal mode :
- automatically when the target temperature is reached, and returns to normal mode,
- either after 5 minutes and setting failure ---> start the cycle again.
You can stop the adjustment cycle during there running time by pressing
NORMAL MODE
Back in normal mode, the electric actuator is inactive, the regulation of the
temperature is mechanically controlled by the bimetallic strip.
22017554_QIM-e-ULTRA-IM-FR-W-ML-01-20-Rev.0
EN
+55°C
+39°C
T
M
M
Draw-off
point
Alarm relay
VM2D VM2C
T
T
M
M
M
A
DHW 65°C
Production or inlet
DHW
production relay
T
+50°C
Thermometer
Manometer
T
M
M
Non-return
Isolation
Shut-off or
check valve
valve
isolation valve
by pressing on
C
Mixed water
+39°C
M
T
Loop-back
T° probe
Mixed water
loop-back
Pump relay
VM1A
VM1B
C
Temperature probe
Pressure tap
T
Balancing
Safety valve
Differential
valve
pressure gauge
or
,
1590 Avenue d'Orange • SORGUES 84275 VEDENE • FRANCE
Phone +33 (0)4 90 33 28 28 • Fax +33 (0)4 90 33 28 29/39
Cold water
All device connection
BMS
IP 55 watertight
case (IP box)
ModBus output
to interface
with a BMS
Anti-micro
cut-off device
PROGRAMMING
CONTROL UNIT
Flush relay
Cold water
Solenoid
Drain
Actuator
Pump
A
Air vent
Water
meter
C
Mixed T° setting
55.0
°C
Mixed T° setting
55.0
°C
Mixed water
50.5°C
Thu 18/10/19
10:52
55.0
Mixed Water
Temperatur e
Loopback
51.3°C
DHW
65.4°C
Normal
WATTS INDUSTRIES France
contact@wattswater.com • www.wattswater.fr
220V AC
Filter
Pressure
reducing valve
SD
°C