Daikin EKOMB22AAV1H Instructions D'installation page 29

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 111
5.10.3
Permitted pipe lengths at parallel air supply and flue tube systems
Permitted pipe lengths when applying Ø80 mm (total of flue pipe and air intake pipe
together).
C13
EKOMB22AAV1
100 m
EKOMB28AAV1
EKOMB33AAV1
Replacement lengths
Bend 90°
R/D=1
Bend 45°
R/D=1
Knee 90°
R/D=0.5
Knee 45°
R/D=0.5
Calculation example
Pipe
Pipe lengths
Flue gas outlet
L1 + L2 + L3 + 2x2 m
Air supply
L4 + L5 + L6 + 2x2m
Note:
The total pipe length is: sum of the straight pipe lengths + sum of the replacement pipe
lengths of bends/knees amounts to a total of 25 meters. If this value is less than the
maximum permitted pipe length, the flue gas outlet meets the requirements on this point.
Daikin Europe NV
C33
C43
C53
100 m
100 m
100 m
85 m
85 m
85 m
85 m
80 m
80 m
80 m
80 m
2 m
1 m
4 m
2 m
Pipe length total
13 m
12 m
C83
100 m
85 m
80 m
29