LG DLEX3550 Série Mode D'emploi page 27

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Connecting electric dryers (cont.)
USA only
WARNING
w
• Connect the power cord to the terminal block. Each colored
wire should be connected to same color screw. Wire color
indicated on manual is connected to the same color screw
in block. Failure to follow these instructions may result in a
short or overload.
• Grounding through the neutral conductor is prohibited
for: (1) new branch-circuit installations, (2) mobile homes,
(3) recreational vehicles, and (4) areas where local codes
prohibit grounding through the neutral conductor.
three-wire connection for electric dryers: direct wire
• A 3-wire connection is NOT permitted on new construction after
January 1, 1996.
• A UL-listed strain relief is required.
1
1. Remove 3
⁄₂ inches (8.9 cm) of the outer covering from the wire.
Strip 1 inch (2.5 cm) insulation from each wire. Bend the ends of
the three wires into a hook shape.
2. Remove the terminal block access cover on the upper back of
the dryer. Install a UL-listed strain relief into the power cord
through-hole; then thread the power cable prepared in Step 1
through the strain relief.
1" (2.5 cm)
Terminal Block
UL-Listed
Strain Relief
UL-Listed
3-Wire
Power Cord
INStALLAtION INStRUCtIONS
• Use UL-listed 3-wire #10 AWG-minimum copper conductor
cable.
• Allow at least 5 ft. (1.5 m) length to allow for removal and
reinstallation of the dryer.
3. Attach the two hot leads of the power cord to the outer
terminal block screws. Attach the neutral wire to the center
terminal block screw. Connect the external ground (if required
by local codes) to the green ground screw. TIGHTEN ALL
SCREWS SECURELY. Reinstall the terminal block access cover.
Hot
(Black)
Ground Screw
Ground Wire
27
Neutral
Hot
(White)
(Red)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Dlgx3551 série

Table des Matières