SECTION 4 |
occurs earlier):
a) When the 4 Hr / 8 Hr Absorption Stage Timer (Selected by DIP Switches "S3" and
"S4"- See Section 7.5, Table 7.3) runs out OR,
b) When the charging current tapers down to 10% of the rated "Bulk Current Capac-
ity" of the charger;
• 5A +/- 0.5A for SEC-1250UL
• 3A +/- 0.5A for SEC-2425UL
4.3.2.3.3 Thresholds of Charger Currents for Change over Between Absorption and
Float Stages: The thresholds of charger current for change over between the Absorption
Stage (Displayed as "Absorption"/"U0 Phase" in optional Remote Control 900-RC) and
Float Stage (Displayed as "Float"/"U Phase" in optional Remote Control 900-RC) are
shown below:
Change Over
From Absorption Stage (Level 2) to Float Stage
From Float Stage to Absorption Stage (Level 1)
4.3.2.3.4 Charging Characteristics during Absorption Stage
• Absorption Stage Levels 1 and 2 (Displayed as "Absorption"/"U0 Phase" in op-
tional Remote Control 900-RC) feed additional 35% to 55% of the capacity that
adds to the total charged capacity of around 115% to take care of around 15%
loss due to charger efficiency
• There will be moderate gassing during this Absorption Stage
• Orange LED marked "Absorption"/"U0 Phase" on the optional Remote Control
Model No.900-RC will be lighted
4.3.2.4 Thresholds of Charger Currents for Change over Between Absorption and Float
Stages: The thresholds of charger current for change over between the Absorption
Stage (Displayed as "Absorption"/"U0 Phase" in optional Remote Control 900-RC) and
Float Stage (Displayed as "Float"/"U Phase" in optional Remote Control 900-RC) are
shown below:
Change Over
From Absorption Stage (Level 2) to Float Stage
From Float Stage to Absorption Stage (Level 1)
4.3.3 Stage 3 - Float Stage
4.3.3.1 During this stage, the charger outputs a constant Float Voltage of (i) 13.5V for
SEC-1250UL or, (ii) 27.0V for SEC- 2425UL. This helps in maintaining full capacity of the bat-
tery and also provides replacement charge to overcome self discharge of the battery. The
battery can remain connected in this stage indefinitely without the risk of discharging.
Principles of Operation
SEC-1250UL SEC-2425UL
5A +/- 0.5A
3A +/- 0.5A
10A +/- 0.5A 6A +/- 0.5A
SEC-1250UL SEC-2425UL
5A +/- 0.5A
3A +/- 0.5A
10A +/- 0.5A 6A +/- 0.5A
SAMLEX AMERICA INC. | 15