Technical Data; Plug And Socket Ghg 518 - CEAG GHG 518 45 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code Zone 2
3-pol. + PE
3-pol. + N + PE
Dimensions in mm
X = fixing dimensions
Wall socket,
4- and 5-pole
Explosion protected plug and socket system 63A, GHG 518
1

Technical data

1.1

Plug and socket GHG 518

Marking acc. to 94/9/EC:
EC type examination certificate:
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
Special versions permit deviating temperatures.
Perm. storage temperature in original packing:
Protection category acc. to EN/IEC 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to EN/IEC 61140:
Cable entry:
wall socket
plug
Supply terminal:
wall socket
plug
Test torques:
Cap nut of the M 50 entry
Cover screws
Terminals, plug
Terminals, wall socket
Self-cutting screws size 4
Self-cutting screws size 5
Self-cutting screws size 8
Weight:
wall socket
4-pole
plug
4-pole
wall socket
5-pole
plug
5-pole
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
II 3 G
PTB99 ATEX 1115
up to 690 V, 50/60 Hz
max. 63 A
max. 63 A
max. 80 A gL
up to 690V / 63A
-20° C to +40° C (catalogue version)
-40° C to +80° C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
1x M50 (Ø26-34mm) + 1x blanking plug M50
Ø 19 - 34 mm
Cross section
2 x 4 - 25 mm²
(with cable lugs 1 x 35 mm²)
1 x 4 - 16 mm²
(with cable lugs 1 x 25 mm²)
5.0 Nm
2.5 Nm
4.5 Nm
3.5 Nm
2.0 Nm
3.0 Nm
3.5 Nm
(catalogue version)
GHG 518 44
approx. 8.10 kg
GHG 518 74
approx. 0.75 kg
GHG 518 45
approx. 8.15 kg
GHG 518 75
approx. 0.80 kg
690 V VAC
20 A
AC 15
DC 13
Plug, 4- and 5-pole
Cooper Crouse-Hinds
Ex nC IIC T5/T6
Stripped wire length
19 mm
12 mm
400V / 6A
24V / 2A
7 7 7 7 7

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ghg 518 75

Table des Matières