PESD
Approvals:
UL LISTED file No. E334957
Per ISA 12.12.01-2007
CAT REPORT No. E188860-A3
per UL61010-1, 3
CAN/CSA-C22.2 No. 61010-1, 3
Input
AC SINGLE or 3-P DELTA or WYE:
20 to 600VAC
DC OR STORED ENERGY:
20 to 1000VDC
Maximum Rating
750VAC
Detection
Flashing : 14VAC
Thresholds
Solid- ON : 15VAC
Temperatures
Operate : -20C to +55C, Code T6
Storage : -45C to +85C
Terminations
3 Ft. Stranded Cu. Wires, 12 AWG 90° @1000V,
UL-1452 PVC Insulation w/ nylon jacket
Wire
4-Wire : L1- L3: BLK w/ bar code, GND: Grn/Yel (Fig. 1)
5-Wire : L1- L3 + N: BLK w/ bar code, GND: Grn/Yel, N: Wht Neutral (Fig. 2)
Indicators
4-Wire : (6) Red L1-L3, (2) Amber GND LEDs, Fully Encapsulated
5-Wire : (6) Red L1-L3, (4) Amber N & GND LEDs, Fully Encapsulaed
Enclosure
Threaded Base & Channel Ring Lexan 940 BLK,
Cover Lexan 943
Totally Encapsulated for Environment Protection
O-Ring Seals
#118 & #123 Blue FVMQ Flourosilicone,
UL approved material
EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENT MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
Edition
RD
Edition
RD
, Line-to-Line, 50/60/400 Hz
3
, (Voltages Line-to- Line or Line-to-Ground)
3
or 1000VDC
@ 1.2 Watts, Operating Ambient Air of 55°C Max.
, 18.5VAC
, 15VDC
3
1
, 19VAC
, 17VDC
3
1
CAT III 1000V
CAT IV 600V
DC or AC-rms to Ground
(Peak Impulse Transient 8000V
20 repetitions, 2 ohm source)
(typical cut-off's)
(typical cut-off's)
9
IP67
UL TYPE 4X
TYPE 12
MEASURING EQ. 46RD
TYPE 13
3 Phase, 4- Wire
Fig. 1
3 Phase, 5- Wire
Fig. 2
SYMBOL IDENTIFICATIONS
3
3 Phase AC rms
DC Volts
Electric Shock Danger of Death
Caution
Double Insulated Symbol
IND. CONT. EQ. 496Y
HAZ. LOC. 42 RV

Publicité

loading

Ce manuel est également adapté pour:

Pesd safeside r-3d2Pesd safeside r-3d2-w5Pesd safeside r-3d2-srPesd safeside r-3d2-srw5