Technical Data; Accessories - Riello RS 300/E BLU Manuel D'entretien

Table des Matières

Publicité

TECHNICAL DATA

MODEL
TYP
max.
OUTPUT
(1)
min.
FUEL
Gas pressure at maximum delivery.
OPERATION
STANDARD APPLICATIONS
AMBIENT TEMPERATUR
COMBUSTION AIR TEMPERATURE
ELECTRICAL SUPPLY
FAN MOTOR
(star-delta starting for RS400 - 500 - 800)
IGNITION TRANSFORMER
ELECTRICAL POWER CONSUMPTION
ELECTRICAL PROTECTION
CONFORMITY TO EEC DIRECTIVES
NOISE LEVELS
(EN 15036-1)
(3)
APPROVAL
Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Pressure at pressure switch test point 20)(A)p.12 with zero pressure in the combustion chamber and maximum burner output.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3)

ACCESSORIES

(optional)
OUTPUT POWER REGULATOR KIT:
rates between the low and high flame output position, thus ensuring stable operating conditions in terms of temperature or pressure. Two compo-
nents should be ordered: • Power regulator to install to the burner; • probe to install to the boiler.
PARAMETER TO BE CHECKED
Temperature
Pressure
• KIT AZL (display and operating unit)
• INFRARED SENSOR KIT QRI
• PRESSURE SWITCH KIT (for leak detection control)
• KIT SOFTWARE INTERFACE
• SOUNDPROOFING BOX KIT
GAS TRAIN ACCORDING TO REGULATION EN 676
Note.
Riello S.p.a. declines all responsibility for the addition of safety devices not provided for herein.
kW
kW
Gas: G20/G25
mbar
(2)
°C
°C max
rpm
V
kW
A
V1 - V2
I1 - I2
kW max
dBA
class 3 (EN 676)
CE
Under modulating operation, the burner automatically adapts to one of an infinite number of firing
Range
- 100...+ 500°C
0...2,5 bar
0...16 bar
RS 300/E BLU
RS 400/E BLU
849 T1
850 T1
1350 ÷ 3800
1830 ÷ 4590
500
950
NATURAL GAS: G20 (methane) - G21 - G22 - G23 - G25
23,3 / 32,7
34,3 / 40,2
Continuous / Intermittent
Boilers: water, steam, diathermic oil
3N ~ 400 / 230V +/-10% 50 Hz
2900
2900
230/400
400/680
4,5
7,5
15,8 - 9,1
16 - 9
6
98/37 - 90/396 - 89/336 - 73/23
82
0085BO0341
0085BO0341
PROBE
Type
PT 100
Output probe
4...20 mA
Code 3010355
Code 3010354
Code 3010344
Code 3010388
code 3010376
: see page 22.
8
RS 500/E BLU
856 T1
2500 ÷ 5170
1000
37,6 / 56,1
0 - 40
60
2900
400/680
9,2
18 - 10,5
230 V - 1 x 8 kV
1 A - 20 mA
10
11
IP 54
85
88
0085BO0341
POWER REGULATOR
Code
Type
3010110
RWF40 BASIC
3010213
RWF40 HIGH
3010214
RS 800/E BLU
887 T1
3500 ÷ 8100
1200
45.5 / 81.2
2900
400/690
21
40 - 23
25
91
Code
3010356
3010357

Publicité

Table des Matières
loading