CLEARANCES TO COMBUSTIBLES

It is of utmost importance that the clearances to combustible materials be strictly adhered to during
installation of the stove. Refer to the tables below.
A
20(14)
(508mm(356mm))
(559mm(508mm))
Floor to ceiling height must be at least 7' (2.13m) in all cases.
Do not place any combustible material within 4' (1.2m) of the front of the unit.
The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue pipe.
The chimney connector must not pass through an attic or roof space, closet or similar concealed space, a
floor, or a ceiling.
For Canadian installations, where passage through a wall, or partition of combustible construction is
desired, the installation must conform to CAN/CSA-B365.
A flue pipe crossing a combustible wall must have a minimum clearance of 18" (457.2mm).
To reduce flue clearances from combustible materials, contact your local safety department.
Single Wall Pipe (Double Wall Pipe)
B
C
22(20)
22.5(16.5)
(572mm(419mm))
D
32(30)
(813mm(762mm))
(305mm(279mm))
-7-
E
F
12(11)
22(21)
(559mm(533mm))