The LV38 is installed into a rectangular opening. It is best to frame your appliance after it is positioned and the
vent system is installed. Use the steel stud frame provided.
SEE-THROUGH
Maintain these minimum clearances to combustibles from appliance and vent surfaces:
Appliance framing:
Use steel stud framing provided.
Non- Combustible Appliance fi nishing:
Front -
7" (178mm) to sides of appliance opening
-
26 1/2" (67.3cm) above appliance opening
Combustible Appliance fi nishing:
-
64" (162.6cm) from bottom of appliance to enclosure top
-
3" (76mm) to top of vent pipe*
-
2" (51mm) to sides and bottom of vent pipe*
Non-combustible fi nishing material (ie. cement board, brick, stone, tile) must be used to fi nish the front of
the appliance.
SINGLE-SIDED
Maintain these minimum clearances to combustibles from appliance and vent surfaces:
Appliance framing:
Use steel stud framing provided.
Non- Combustible Appliance fi nishing:
Front -
7" (178mm) to sides of appliance opening
-
26 1/2" (67.3cm) above appliance opening
Combustible Appliance fi nishing:
-
55" (139.7cm) from bottom of appliance to enclosure top
-
3" (76mm) to top of vent pipe*
-
2" (51mm) to sides and bottom of vent pipe*
Non-combustible fi nishing material (ie. cement board, brick, stone, tile) must be used to fi nish the front of
the appliance.
*HORIZONTAL VENT SECTIONS: A minimum clearance of 3" (76mm) to the top and 2" (51mm) to the sides
and bottom of the vent pipe on all horizontal runs to combustibles is required. When passing through a wall,
use fi restop spacer W615-0112 (supplied).
Horizontal vent sections within enclosures require a minimum clearance of 3" (76mm) at the top of the vent
pipe, see "MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES" section and 1" (25mm) to the sides of
the vent pipe.
*VERTICAL VENT SECTIONS: A minimum of 1" (25mm) all around the vent pipe on all vertical runs to
combustibles is required. When passing through a ceiling, use fi restop spacer W500-0028 (not supplied).
27
EN
W415-1539 / B / 11.22.16