7
NZM4-XKSA
Z 2
1 Nm
(9 lb-in)
Z 2
2 Nm
(18 lb-in)
NZM4(-4)-XKB
1
F 1100 A
4
2
16 mm
50 Nm
(443 lb-in)
2/2
Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
© 2002 by Eaton Industries GmbH,
www.eaton.com/moeller/support
ON
2
M10 metric size hardware, provided with all kits, connects to double hole per phase
configuration on NZM4 breaker or switch.
5
NZM4-XKSA
1
1
f 6 x 16 x 0.8 mm
F 2 x (10 x 32 x 1.0) mm
Warning!
Use of the NZM4-XKSA Terminal Cover is required at
all times to maintain proper electrical clearances when
using the NZM4-XKB... Flexibus Clamp Connectors.
Emergency On Call Service: Local representative (http://www.eaton.com/moeller/aftersales) or +49 (0) 180 5 223822 (de, en)
No more than 2 mm (0.08") of screw
thread must show when conductor is securely attached.
F 2 mm (F 0.08")
> 2 mm (> 0.08")
Warning!
Use of the NZM4-XKSA Terminal Cover (provided) is
required at all times to maintain proper electrical
learances when using the NZM4-XKA... Mechanical
(Tunnel) Lug Connectors.
3
1
6
2
NZM4-XKSA
5 mm
3
6 Nm
Z 2
(53 lb-in)
1 Nm
(9 lb-in)
f 6 x 0.63" x 0.03"
F 2 x (10 x 1.26" x 0.04")
All Rights Reserved
ON
Z 2
2 Nm
(18 lb-in)
07/11 IL01210012Z 12255100/DE17 DHW/DM
Printed in Germany (08/11)