seCtIOn 7 |
- Stage 1 and Stage 3. This also applies when two banks of batteries are being charged
simultaneously and the batteries in the two banks are in a dissimilar state of discharge.
A pair of switches S1 & S2 out of a set of 4 DIP Switches has been provided for selecting
the battery type and for modifying the Stage 2 Absorption Stage when charging loaded
batteries / two banks of batteries with different discharged states. The following selec-
tions can be made with the help of the DIP Switches S1 and S2:
!
cAUtion!
Do not change the DIP Switch setting when the charger is operating. Always
change the DIP Switch setting when the charger is OFF, i.e. after disconnecting
the charger from the AC input power).
note: The voltages are for battery temperature of 77ºF / 25ºC.
DiP SWitcH SettinG FoR Sec-1280UL
S1
S2
off*
ON*
ON
off
off
off
ON
ON
* factory pre-set in this position
DiP SWitcH SettinGS - Sec-2440UL
S1
S2
off*
ON*
ON
off
off
off
ON
ON
* factory pre-set in this position
Preparing the Charger for Operation
Float
13.5V*
13.5V
13.5V
Float
27V*
27V
27V
Absorption
Flooded /
14.4V*
14.0V
battery with
Disabled
caution! Do not use this setting
Absorption
Battery type
Flooded /
28.8V*
28.0V
Gel Cell
battery with
Disabled
caution! Do not use this setting
Battery
charging
type
Stages
3 Stages
AGM*
(Stages 1, 2, 3)
3 Stages
Gel Cell
(Stages 1, 2, 3)
2 Stages
Load
(Stages 1, 3)
charging
Stages
3 Stages
AGM*
(Stages 1, 2, 3)
3 Stages
(Stages 1, 2, 3)
2 Stages
load
(Stages 1, 3)
SAMLEX AMERICA INC. | 21