Technical Data; Accessories - S+S Regeltechnik PREMASGARD 1160 Notice D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASGARD
1160 ⁄ PREMASREG
Calibrateable pressure sensors PREMASGARD
pheric, or differential pressures in air for volume flow rate indication. The piezo-resistive measuring element guarantees a high degree of
reliability and accuracy. Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air
conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement, or for triggering fre-
quency converters. Media measured are air (non-precipitating), or other gaseous non-aggressive, non-combustible media.

TECHNICAL DATA:

Power supply: ............................. PREMASGARD
Power consumption: ................. < 1.1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
Measuring ranges: ..................... 1000 Pa ⁄ 5000 Pa
Output signal: .............................. 0 -10 V
Electrical connection: ................ 3-wire connection
Media temperature: .................. 0 ... + 50 °C
Pressure connection: ................ 4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm),
Type of pressure: ....................... differential pressure
Medium: ....................................... clean air and other non-aggressive, non-combustible gases
Accuracy: ..................................... ± 1.5 % of pressure range end value (at 20°C)
Sum linearity+hysteresis: ......... < ± 1 % of pressure range end value
Temperature drift values: ......... ± 0.1 % of pressure range end value per °C
Zero point offset: ....................... < ± 0.7 % of pressure range end value
Above- ⁄ below-
atmospheric pressure: ............. max. ± 200 hPa
Signal filtering: ............................ switchable 1 s ⁄ 10 s
Enclosure: .................................... impact-resistant plastic, material polyamide,
Dimensions: ................................. 108 x 72.5 x 70 mm (Thor II)
Electrical connection: ................ 0.14 - 1.5 mm², via removable plug-in screw terminals
Cable gland: ................................. M 16, including strain relief
Humidity: ...................................... < 95 % r.H., non-precipitating air
Protection class: ........................ III (according to EN 60 730)
Protection type:.......................... IP 65 (according to EN 60 529)
Standards: ................................... CE conformity
Features: ..................................... two-line display with illumination, 37 x16 mm (W x H),
K factor: ....................................... 1 to 3000
Measurement units: .................. adjustable
Max. value displayed: ................. 999999
ACCESSORIES:: ........................... including connection set ASD - 06 (nipple straight)
®
1160
®
1160 and PREMASREG
®
1160:
24 V AC (± 20 %) and 15 ... 36 V DC (± 10 %)
®
PREMASREG
1160:
24 V AC ⁄ DC (± 20 %)
metal pressure connection nozzles
30 % glass-globe-reinforced,
with quick-locking screws, c
olour pure white (similar RAL 9010)
according to EMC directive 2004 ⁄ 108 ⁄ EC,
according to EN 61326-1: 2006,
according to EN 61326-2-3: 2006
displaying the volume flow rate
m³ ⁄ s, m³ ⁄ min, m³ ⁄ h, liters ⁄ s, liters ⁄ min, liters ⁄ h
(included in the scope of delivery)
connection nipple ASD - 07 (at 90 degree angle)
®
1160 are used for measuring above-atmospheric, below-atmos-
10

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Premasreg 1160