Especially in cold weather:
Readjust the slope of the heating curve with setting knob
:
-
Room temperature too high: Reduce slope by about 0.2
-
Room temperature too low: Raise slope by about 0.2
Especially in the night:
Readjust the setback with setting knob
indicates the setback in °C against the NORMAL tem-
perature.
Tip: Each time you make a room temperature readjust-
ment, wait two days; the controlled system needs
time to adapt.
Tip: Do not forget objects that are sensitive to low tem-
peratures, such as plants.
You want to change the heating periods
For digital time switch: please refer to separate instructions.
Set the periods of time for the NORMAL temperature and
REDUCED/OFF with the switching dial using the tilting
riders:
-
For periods of time with NORMAL temperature:
Tilt riders outward
-
For periods of time with REDUCED temperature or
OFF: Tilt riders inward
Tip: Before making any settings: Prepare a heating
schedule.
Only with the RVP210: You want to
change the d.h.w. temperature
Readjust the d.h.w. temperature with the setting knob
Recommended setting: 55 to 60 °C.
Tip: Excessive temperatures lead to more scale buildup.
Your heating system responds in an
unusual manner
-
In the event of a power failure, the clock will make up
for the lost time when power returns.
You can cancel catching up by briefly setting the se-
lector to
and then back again to the required oper-
ating mode. Then, readjust the clock
-
Temperature does not change: Check the operating
mode; automatic setback and heating up with only one
mode
-
Room unit (if present) is inactive: Check the controller's
operating mode – it must be an
-
Required temperature is reached either too early or to
too late: Change the 24-hour program
Tip: Well insulated buildings have a great thermal inertia.
What to check in the case of operational
faults
-
Are all fuses of the plant in order?
-
Is sufficient fuel in the tank?
-
Have the controller settings (e. g. the setpoints) been
changed?
-
Does the green LED «Override» flash? Reason: Flow
or boiler temperature sensor faulty / not connected, or
outside and room temperature sensor
faulty / not connected. Select operating mode
call in your heating engineer
-
Has the burner gone to lockout? If yes, press the reset
button
Energy saving tips
-
Do not allow room temperatures to exceed 21 °C during
the day
-
Air the rooms for only short periods of time, but with the
windows fully open
-
Set the thermostatic radiator valves in unoccupied
rooms to the frost protection position
-
Make certain there are no curtains, furniture, etc., in
front of the radiators
-
Close shutters and blinds whenever possible
-
Check the consumption of heat on a regular basis