3.3.2. Setting according to the batteries type
Switches setting
A
B
C
D
0
0
0
0
1
0
0
0
0
1
0
0
1
1
0
0
0
0
1
0
1
0
1
0
0
1
1
0
1
1
1
0
0
0
0
1
0
1
1
1
1
1
1
1
(*) Voltage on + BAT 1, + BAT 2 and + BAT E with 10% of the rated current and a tolerance of +/- 1%.
(
)
REFRESH is not advised for certain types of AGM batteries
**
Some specific settings are possible – please consult us.
3.3.3. Temperature compensation
The TEMP-AL sensor enables the compensation of Absorption voltage and
Floating Voltage depending on the ambient temperature of the battery room.
The adopted coefficient is -18mV/°C.
Description of the
battery type
Opened type bat
free electrolyte (wet)
Classic sealed type
bat
(Sealed Lead)
GEL type bat
AGM type bat**
Spiral type bat
Tin calcium lead bat
Wintering or standby
sealed bat
Stabilized DC power
supply
SPE1 open type bat
PBUS CAN COMMUNICATION (ACE-PBUS or ACE-TFT)
Voltage* U1
Voltage* U2
Charging
Floating
14.1V
13,4V
14.4V
13,8V
FACTORY SETTING
14.4V
13,8V
14.4V
13,6V
14.4V
13,6V
15.1V
14.4V
13.4V
13.4V
12.0V
12.0V
14.8V
13,2V
BUS CAN COMMUNICATION
Maximum
Max. duration of
duration of
ABSORPTION
BOOST (I)
(U1)
6H
6H
6H
6H
6H
6H
6H
6H
6H
6H
6H
6H
0H
0H
0H
0H
6H
6H
26