Daikin EDLQ036BA6VJU1 Manuel D'installation page 29

Masquer les pouces Voir aussi pour EDLQ036BA6VJU1:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

[2] Disinfection function
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic water to a specific temperature.
CAUTION
The disinfection function field settings must be configured
by the installer according to local laws and regulations.
[2-00] Operation interval: day(s) of the week at which the
domestic water should be heated.
[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).
[2-02] Start time: time of the day at which the domestic water
should be heated.
[2-03] Set point: high water temperature to be reached.
[2-04] Interval: time period defining how long the set point
temperature should be maintained.
T
DHW
[2-03]
T
H
T
U
00.00
01.00
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
T
High set point temperature [2-03]
H
t
Time
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local laws and regulations.
[3] Auto restart
When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.
NOTE
It is therefore recommended to leave the auto restart
function enabled.
Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the pr button to enable the schedule timer again.
[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).
NOTE
If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56182-1
[2-04]
22.00
23.00
24.00
t
[2-02]
[4] Backup heater operation and space heating off temperature
Backup heater operation
The operation of the backup heater can be enabled or disabled, or it
can be disabled depending on operation of the booster heater.
[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).
NOTE
Even in case the backup heater operation
status field setting [4-00] is set to disabled (0),
the backup heater can operate during start-up
and defrost operation.
[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1), or if the backup heater operation has priority
over the booster heater operation (2).
When the priority field setting is set to ON (1),
NOTE
space heating performance of the system
might
be
temperatures, since in case of domestic water
heating demand the backup heater will not be
available for space heating (space heating will
still be provided by the heat pump).
When the priority field setting is set to ON (2),
domestic water heating performance of the
system might be decreased at low outdoor
temperatures, since in case of space heating
demand the booster heater will not be
available for domestic water heating. However
domestic water heating by heat pump will still
be available.
When the priority field setting is set to OFF (0),
make sure that electrical power consumption
does not exceed supply limits.
Space heating off temperature
[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.
decreased
at
low
outdoor
Installation manual
27

Publicité

Table des Matières
loading

Table des Matières