Liens rapides

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
48P21-811 Air Handler Control
Thermostat Harness Assembly
(for replacing old board 47-100436-04)
Updated Unit Wiring Diagram
The 48P21-811 is an aftermarket OEM Direct replacement control kit for Rheem air handlers with PSC blower
motors.
ELECTRICAL RATINGS:
Input Voltage:
25 VAC, 50/60 Hz (Class II transformer)
Operating Temperature Range:
-40° to 175°F (-40° to 80°C)
Humidity Range:
5 to 95% relative humidity
(non-condensing)
Agency Approvals:
UL
TIMINGS:
Thermostat
Blower
Input
ON Delay
G
2 seconds
W1 or W2
2 seconds
NOTE: All wiring should be installed according to local and
national electrical codes and ordinances.
1.
Disconnect electrical power, then remove unit access
panels.
2.
If unit already contains the newer control design with a
pin header for thermostat connections, simply replace
the board and discard the wiring harness and updated
wiring diagram. Otherwise:
3.
Remove old board from bracket leaving all wiring
connected to it. Mount new board in its place.
4.
If unit has a heater kit disconnect wiring harness coming
from heater and plug directly into new board.
INSTALLATION INSTRUCTIONS
5 - Wire Nuts
2 - Wire Ties
Installation Instructions
Blower
OFF Delay
30 seconds
75 seconds
INSTALLATION, MOUNTING AND WIRING
5.
Transfer the following quick-connect wiring points from
the old board to the new board: "XFMR-R", "XFMR-C",
"COM". Disconnect and remove the piggyback terminal
on the "C" connection which leads to the old heater kit
connector. See Figure 1 below.
6.
Transfer fan relay connections. Note that one is no longer
used. The wire connected to this point should also be
removed from the wire nut connection point at the other
end of the wire.
7.
Connect the wiring harness included with this kit to
the 5-pin terminal on the new board. Match the color
coding on the thermostat wiring with the wires on this
white-rodgers.com
emerson.com
48P21-811
Rheem Air Handler Control for
PSC Blower Motor
PARTS INCLUDED
SPECIFICATIONS & TIMINGS
CAUTION
!
Risk of Electric Shock.
Disconnect electric power
to system until installation
is complete. Do not use on
circuit exceeding specified
voltage. Higher voltage will
damage control and could
cause shock or fire hazard.
This control is not intended
for use in locations where
it may come in contact with
water.
May cause flame rollout.
Shut off main gas to heat-
ing system until installa-
tion is complete.
DESCRIPTION
PART NO. 37-7726001
1815

Publicité

loading

Sommaire des Matières pour Emerson White-Rodgers 48P21-811

  • Page 1 5-pin terminal on the new board. Match the color If unit has a heater kit disconnect wiring harness coming coding on the thermostat wiring with the wires on this from heater and plug directly into new board. PART NO. 37-7726001 white-rodgers.com emerson.com 1815...
  • Page 2 Gather excess wiring and secure with wire ties. Route power to the unit. Verify unit operation. wiring through opening in the side of the cover, it should WIRING DIAGRAM Emerson and White-Rodgers are trademarks of Emerson Electric Co. white-rodgers.com ©2018 Emerson Electric Co. emerson.com All rights reserved.
  • Page 3 Notez que l’un d’entre eux n’est plus utilisé. Le fil le câblage branché. Montez la nouvelle carte en place. branché ici doit aussi être retiré du capuchon de Si l’appareil est pourvu d’une trousse de chauffage, connexion sur l’autre extrémité du fil. DE PIÈCE 37-7726001 white-rodgers.com emerson.com 1815...
  • Page 4 L2 (240 V c.a.) COMMUN 24 V c.a. STADE DE CHAUFFAGE STADE DE CHAUFFAGE THERMOSTAT APPAREIL DE CHAUFFAGE ÉLECTRIQUE (JUSQU’À 4 STADES) Emerson et White-Rodgers sont des marques de commerce d’Emerson Electric Co. white-rodgers.com ©2018 Emerson Electric Co. emerson.com Tous droits réservés.