Press the MODE / Enter key to acc ess the s ub- menu.
!
ALARM
Insert
maintenance password
Prg
ON
OFF
Entering the c orrect pass word and s uccessi vel y pressing the MODE /
Enter key, access the followi ng mas ks .
Temperature
Band
05.0°C
NOTE: This mas k is onl y displayed if the Adapti veFunction Plus
functi on is enabled.
W inter temperature
Set-point limits
Low
30.0°C
High
50.0°C
Summer temp erature
Set-point limits
Low
04.0°C
High
20.0°C
Enable Ad aptive
Function Plus:
Disable
W inter temp. Setp.
Limits (econom y)
Low
30.0°C
High
38.0°C
Summer temp . Setp.
limits (econom y)
Low
05.0°C
High
10.0°C
NOTE: Thes e two mas ks are onl y displ ayed if the Adapti veFunc tion
Plus function is enabled.
Enable double
set-point
DISABLED
W inter temperature
Double setp. limits
Low
30.0°C
High
50.0°C
Summer temp erature
Double setp. limits
Low
04.0°C
High
20.0°C
NOTE: Thes e mas ks are onl y displayed if the double Set-point func tion
is enabled.
Set-point
By analogu e input
ENABLED
SHIFTING SET-POINT
MODE
0000
Regulation band for c ontrol on
evaporator input water temp.
Set-point s etting limits
Winter
Lower
Upper
Set-point s etting limits
Summer
Lower
Upper
Enabling of Adapti veF uncti on Plus
functi on
Enabled/Disabled
Winter Economy function Set-point
setting limits
Lower
Upper
Summer Economy functi on Set-point
setting limits
Lower
Upper
Enabling double
Set-point func tion
Disabled (Enabled)
Double Set-point setting limits
Winter
Lower
Upper
Double Set-point setting limits
Summer
Lower
Upper
Enabling of Set-point function from
anal ogue input.
Offset/Shifting Set- point Mode
Summer compensation
Set_air
15.0°C
Delta_air
15.0°C
Offset_water
-8.0°C
W inter compensation
Set air
20.0°C
Delta air
-25.0°C
Offset water
08.0°C
NOTE: Thes e two mas ks are onl y displ ayed if the Set- point
compens ation functi on is enabled.
Domestic hot water
Set-point limits
Low
30.0°C
High
50.0°C
Domestic hot water
Tank Setp. limit s
Low
30.0°C
High
50.0°C
Domestic hot water
Set-point
51.0°C
Temp. lim it
53.0°C
Delay
180s
NOTE: Thes e mas ks are displayed onl y if the DHW production function
is enabled/implemented.
(*) This mas k is onl y displayed if the DHW production function from
anal ogue output is enabl ed.
Additional h eater
Offset
01.5°C
Delay
005m in
PL evaluation:
075%
Additional h eater
By external temp.
Set-point
05.0°C
Hyst.
03.0°C
OFF Compressor s
by ext ernal t emp.
Set-point
05.0°C
Hyst.
03.0°C
NOTE: Thes e three mas ks are only displ ayed if the integrati ve
resistance function is enabled.
(*) These mas ks are onl y displayed if the integrative resistance function
is enabled on the basis of the outdoor temperature.
Enable pr essostatic
valve
(*): Only for models TCHEY–THHEY 105÷112 and TCHEY–THHEY
115÷240.
Enable remote on/off
by supervisor
Enable summer/winter
by supervisor
Enable remote on/off
by GSM Modem
Enable summer/winter
by GSM Modem
Time conden ser fan
pre-ventilation
000s
Time post-ventila.
after HP alarm
60s
Anti-freeze heater
Offset
01.5°C
Hyst.
01.0°C
Anti-freeze alarm
Set-point
02.5°C
Hyst.
02.0°C
55
CONTROL PANELL PGD
Set-point c ompensati on i n summer mode
Set-point c ompensati on i n winter mode
Winter Set-point setti ng limits
for production of the DHW
Lower
Upper
Winter Set-point setti ng limits
for DHW produc tion (*)
Lower
Upper
Setting the Set- point for production of
DHW.
Max temp. for DHW
Activation delay
Integrati ve resistance acti vati on
Offset
Delay
Load frac tion
Integrati ve resistance acti vati on on the
basis of outdoor temperature (*).
Set-point
Differential
Compress ors s witch-off on the basis of
outdoor temperature (*).
Set-point
Differential
Enable management of pr essostatic
N
val ve (*)
Enable ON/OFF from super visor
Y
Enable s ummer/winter from super visor
Y
Enable ON/OFF remote from GSM
N
modem
Enable s ummer/winter from GSM
N
modem
Setting pre-ventilation time
Setting ventilati on time after high
pressure i nter vention
Anti-freez e resistance
Offset
Differential
Anti-freez e al arm
Set-point
Differential