I.3.4 Set-Point Compensation; I.3.5 Integrative Resista Nce (Krit); I.3.6 Keypad-Modifiable Variables - RHOSS Mini-Y TCAEY 105/111 Mode D'emploi

Commandes électroniques
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

W inter CS chart in Offset logic
3
2
1
0
-1
-2
-3
4
6
8
10
Example:
With a minimum Offs et of -3°C and a maximum Offs et of 3°C, with an
external analogue signal equal to 16 mA, the Set-point set is increas ed
by 1.5°C.
T
Variation with res pect to the Set-point s et
S
External analogue signal (4÷20 mA)
I.3.4
Set-point Compensation
The Set-point c ompensati on func tion on the basis of the outdoor
temperature c arries out the algebra s um between the Set-point value
set and an offs et value calcul ated depending on the temperature of the
outdoor air. It is possibl e to decide whether to acti vate the func tion in
both functioning modes (summer/winter) or onl y in one.
This func tion is not availabl e if the Scrolling Set-point (CS) functi on is
enabled.
The followi ng mas k is displ ayed if the c orrespondi ng func tion has been
implemented.
Set-point
compensation
Enable summer
N
Enable winter
N
I.3.5
Integrativ e resistance (KRIT)
The el ectric resistance (KRIT access ory) acts as integration i n winter
mode (onl y on machi ne i n heat pump mode). If enabl ed, this func tion
allows to manage the integrative resistance. The integrative resistance
can be managed on the basis of the outdoor air temperature. In this
case the presence of a probe is necess ary (KEAP acc essor y).
The integrative resistanc e function based on the temperature of the
outdoor air is not available if the Scrolling Set-point (CS) functi on is
enabled.
The followi ng mas k is displ ayed if the c orrespondi ng func tion has been
implemented.
Additional H eater
ENABLED
External temp. prob e
DISABLED
Press the Prg key for 3 s econds to go bac k to the previ ous menu.
12
14
16
18
20
S (mA)
Enabling Set-point compens ation
functi on.
Enab. Summer functioning mode
Enab. Winter functioni ng mode
Enabling integrati ve r esistance
Enabling outdoor air temp. probe for
integrative resistanc e management
I.3.6
Keypad-modifiable variables
TCAIY-THAIY 124÷150
Function
Cooling set point
Heating set point
Remote Summer/Winter
Pass word
TCAEY-THAEY 270÷4320
Function
Set-point Cooling Precision
Set-point Heating Precision
Set-point Cooling Economy
Set-point Heating Ec onomy
Set-point Heating Ec onomy
for radiating sys tems
Remote Summer/Winter
Pass word
TCAEY 279÷2189
Function
Set-point Cooling Precision
Set-point Cooling Economy
Pass word
TCHEY-THHEY 115÷240
Function
Cooling set-point
Heating set- point
Remote s ummer/winter mode
Pass word
TCHEY-THHEY 245÷4450
Function
Cooling set point
TCHEBY (HT-LT)
Cooling set point
THHEBY (HT-LT)
Heating set- point
THHEBY HT
Heating set- point
THHEBY LT
Remote s ummer/winter
Pass word
52
CONTROL PANELL PGD
Regulation
Default value
5 ÷ 20°C
7°C
30 ÷ 53°C
45°C
N
Technical Assistance
Regulation
Default value
4 ÷ 20°C
7°C
30 ÷ 53°C
45°C
5 ÷10°C
-
42 ÷ 50°C
-
32 ÷ 45°C
-
-
N
Technical Assistance
Regulation
Default value
4 ÷ 20°C
7°C
5 ÷10°C
-
Technical Assistance
Regulation
Value set
4 ÷ 18°C
7°C
30 ÷ 55°C
45°C
N
After-sales assistance
Regulation
Set value
4 ÷ 23°C
7°C
4 ÷ 20°C
7°C
30 ÷ 55°C
45°C
30 ÷ 52°C
45°C
N
After-sales Assistance