External Silicagel Cartridge; Inspection And Repair - ITRON Fluxi 2000/TZ Mode D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 7
a) On commissioning to fill the volume between
the pump and the bearings
DN
Oil vol. (cm
50/80
100
150/200
≥250
b) In Service
DN
Oil vol. (cm
50/80
100
150/200
≥250
c) Recommended lubrication periodicity
Application
Dry gas, no dust
Gas comprising light condensates
and little dust
Gas with high percentage of
condensates and dust
BIOGAS applications

5.2. External silicagel cartridge

The meter can be equipped with an external silica-
gel cartridge for installation in severe environment
conditions. To replace the cartridge, unscrew the
old cartridge, remove the protective plug of the
new cartridge and screw it into the totaliser.

5.3. Inspection and repair

The proper installation and functioning of the me-
ter can be verified by a visual control of the tota-
liser (to check that the meter runs properly). It is
possible to check the good functioning of the Fluxi
2000/TZ by applying a spin test. This test will give
information about eventual friction in the turbine
ball bearings.
6
)
Push
3
4
20
5
25
6
30
7
35
)
Push
3
0,5
2-3
0,8
4
1,0
5
1,2
6
Lubrication
periodicity
6 months
Monthly
Weekly
The test has to be conducted as follow:
– Accelerate the turbine wheel around 30 to
50% of Qmax then to measure the time until
the turbine wheel stops.
– Measure the spin time (ST) until the turbine
wheel stops.
See Annex 6 for typical values of spin time.
The following recommendations have to be ob-
served for repair:
• I n case of use with aggressive or dangerous gas,
it may be necessary to send a safety statement
with the meter, detailing the type of Gas that
has been measured.
• S ome gas may still be present inside the meter
and the pipe; therefore sufficient ventilation is
required.
• R epairs and maintenance must be done by trai-
ned or qualified personal. Afterwards a tight-
ness test with 1.1 x PS (Pmax) must be perfor-
med.
• W hen changing pressure-bearing parts, ensure
that spare parts that comply with the PED are
used.
• T he right spare parts are traced by providing
the serial number of the meter to Itron and/or
by using the Itron CD ROM "Spare parts cata-
logue".
• I f used with wet gas, internal and external effect
of corrosion has to be checked regularly and in
case of severe corrosion, the meter must be
replaced.
• U se solvent and alcohol free cleaning product
to clean the meter.

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

652-099-2025Fluxi 2000/tz

Table des Matières