6. Technical data METRAVOLT VT 1500:
Nominal voltage
certified in accordance with
range:
IEC 61243-3
0 ... 1000 V AC / 1500 V DC
Display range:
0.03 V ... 1500 V DC
0.15 V ... 1200 V AC
Measurement range/ 0.10 V ... 19.99 V
Accuracy:
20.1 V ... 99.9 V
100 V ... 1200 V AC ± 1 % + 3 D
100 V ... 1500 V DC ± 1 % + 3 D
< 500 Hz (TRMS)
> 500 Hz (Sin eff)
2
Frequency:
16 - Hz ... 10 kHz < 500 V,
3
2
16 - Hz ... 2 kHz > 500 V
3
Display of voltage / phase/ phase sequence:
red LED for voltage,
yellow for phase sequence,
LCD digital display,
bicolour backlight,
7-segment-figure, 2 lines,
0 ... 1999 digit
Display of resistance / continuity / diodes:
green LED for continuity up to
999 kΩ and diodes, LCD
3½-digit for kΩ-reading,
buzzer ≤ 1.00 kΩ for 5 seconds
Measuring range - Resistance:
0.00 ... 999 kΩ
Measuring range - Frequency:
2
16 - Hz ... 99.9 Hz / 100 ... 9999 Hz
3
Input resistance:
317 kΩ at 50 V / 50 Hz
200 kΩ at 1000 V AC,
589 kΩ at 1000 V DC
Current (Peak value):
direct:
switched: < 300 mA at 1000 V
On-time t on / recovery time t off) :
at 230 V / 400 V unlimited
at U
N
Overvoltage category:
CAT IV 1000 V
in acc. to IEC 60664-1 (VDE 0110)
Surge withstand capability:
>19.2 kV housing-insulation
to operator
>12.0 kV circuit between
the test electrodes
Insulation test voltage:
6 kV / 5 s - routine test
housing and connection line
Operating temperatures:
-15°C ... + 55°C
Power supply:
2 x 1.5 V AAA LR03
automatic off after 30 s of
inactivity
multi-stage display of battery
status
Housing:
ABS/PC/TPE,
display cover PC impact resistant,
handle to lock in place,
belt clip
28
± 1 % + 3 D
± 1 % + 3 D
± 10 % + 3 D
(5 % + 5 D)
3.5 mA at 1000 V
2 min t on / 2 min t off