METRAVOLT VT 1500
Spannungs- und Durchgangsprüfer
Voltage-Continuity Tester
Détecteur de tension et de continuité
Gossen Metrawatt GmbH
Südwestpark 15
D-90449 Nürnberg
Telefon +49 911 8602-111
Telefax +49 911 8602-777
E-Mail: info@gossenmetrawatt.com
www.gossenmetrawatt.com

Publicité

loading

Sommaire des Matières pour Gossen MetraWatt METRAVOLT VT 1500

  • Page 1 Bedienungsanleitung 3-349-592-02 Operating Instructions 1/9.20 Mode d’emploi METRAVOLT VT 1500 Spannungs- und Durchgangsprüfer Voltage-Continuity Tester Détecteur de tension et de continuité Gossen Metrawatt GmbH Südwestpark 15 D-90449 Nürnberg Telefon +49 911 8602-111 Telefax +49 911 8602-777 E-Mail: info@gossenmetrawatt.com www.gossenmetrawatt.com...
  • Page 2 rückseitig rückseitig 1 Prüfelektroden 2 Messstellenbeleuchtung 3 rote LED für gefährliche Spannungen ≥ 50 V AC / 120 V DC + Phasenprüfung 4 orangene LEDs für Drehfeldanzeige links/rechts 5 grüne LED „Ω“ für Durchgang 0 ... 999 kΩ 6 Display (LCD) 7 Taste : für Messstellenbeleuchtung und HOLD Funktion...
  • Page 3 1. Anwendung Der METRAVOLT VT 1500 ist ein zweipoliger, digital anzeigender Spannungsprüfer, nach DIN EN 61243-3 (VDE 0682 Teil 401). Mit Ihm können Sie Spannungen von 0 V bis 1000 V AC / 1500 V DC bei Frequenzen bis 2 kHz, sowie Phase, Drehfeldrichtung und Durchgang prüfen.
  • Page 4 Bitte beachten Sie folgende Sicherheitsvorkehrungen:  Die Spannungsangaben auf dem METRAVOLT VT 1500 sind Nennwerte. Der Spannungsprüfer darf nur in Anlagen mit dem angegebenen Nenn- spannungsbereich benutzt werden.  Eine einwandfreie Anzeige ist nur im Tempera- turbereich von - 15° C ... + 55° C sichergestellt.  Gerät nur an den Handhaben anfassen, um die Anzeige nicht zu verdecken und die Prüfelektro- den nicht zu berühren.
  • Page 5  Vor Verwendung des Prüfers ist das Gehäuse und die Messleitung auf Beschädigungen zu überprü- fen. Wenn Beschädigungen zu erkennen sind, darf der Prüfer nicht mehr verwendet werden. Bei starker Verschmutzungen ist der Prüfer vor der Verwendung zu säubern.  Die Lagerung des Spannungsprüfers muss in trockener und sauberer Umgebung erfolgen.
  • Page 6 3.3 Prüfen von Anzeige und Funktion (Eigentest) Nach EN 50110 -1 müssen Spannungsprüfer mindestens unmittelbar vor und nach Möglichkeit auch nach dem Gebrauch auf einwandfreie Funktion überprüft werden. Schritt 1 - Test der Anzeige Für den Eigentest muss das Gerät ausgeschaltet sein.
  • Page 7 4. Messen und Prüfen 4.1 Allgemeine Hinweise Bei einer Spannung ab 12 V schaltet sich der METRAVOLT VT 1500 automatisch ein oder von Durchgangsprüfung auf Spannungsprüfung um. Hinweis: Bei Spannungen unter 12 V muss das Gerät durch den Taster ein- bzw. durch den Taster Ω...
  • Page 8 Hinweis: Sie können Prüfungen oberhalb des nach IEC 61243-3 geprüften Nennspannungsbereiches durchführen. Der maximale Anzeigebereich ist 1200 V AC / 1500 V DC. Die Lastzuschaltung darf hierbei nur bis maximal 1200 V AC / DC betätigt werden. Bei Lastprüfungen im unzulässigem Bereich erfolgt die Warnung „Load“...
  • Page 9 - Prüfen Sie hierzu die Kondensatorspannung - Betätigen Sie beide rückseitigen Taster - Der Kondensator wird entladen 4.5.4 Zähleranlauf prüfen Der METRAVOLT VT 1500 ist durch seine zugeschal- tete Last zum Anlauftest von digitalen Stromzählern geeignet: - Prüfen Sie hierzu die Spannung der Ausgangseite des Zählers zwischen Phase und Neutralleiter.
  • Page 10 4.6 Phase und Drehfeldrichtung prüfen Achtung! Diese Prüfungen funktionieren erst ab Spannungen von 165 V (50 Hz) gegen Erde. Bei diesen Prüfungen muss das Gerät an der Hand- habe des Anzeigeteils fest umfasst werden. Hinweis: Es können isolierende Handschuhe getragen werden. Prüfungen können durch ungünstige Standorte wie Holztrittleitern oder stark isolierende Fußboden- beläge und bei nicht betriebsmäßig geerdeten...
  • Page 11 Prüfspitze. Wird in diesem Betriebsmodus eine Spannung >12 V angelegt, schaltet das Gerät auf Spannung prüfen um. 5. Messstellenbeleuchtung Der METRAVOLT VT 1500 ist mit einer Messstellen- beleuchtung ausgestattet. Drücken Sie vor der Messung den Taster um das Licht ein-/auszuschalten.
  • Page 12 6. Technische Daten METRAVOLT VT 1500: Nennspannung: zertifiziert nach IEC 61243-3 0 ... 1000 V AC / 1500 V DC Anzeigebereich: 0,03 V ... 1500 V DC 0,15 V ... 1200 V AC Messbereiche/ 0,10 V ... 19,99 V ± 1 % + 3 D Genauigkeit: 20,1 V ...
  • Page 13 8. Wartung / Lagerung 8.1 Allgemeine Informationen Der METRAVOLT VT 1500 ist völlig wartungsfrei. Den- noch ist folgendes für den sicheren Betrieb zu beachten: Bewahren Sie Ihren Spannungsprüfer stets in trockenem und sauberem Zustand auf. Das Gehäuse können Sie mit einem mit Isopropanol (Alkohol) oder...
  • Page 14 Diese Anschrift gilt nur für Deutschland. Im Ausland stehen Ihnen unsere jeweiligen Vertre- tungen oder Niederlassungen zur Verfügung. 10. Produktsupport Bitte wenden Sie sich im Bedarfsfall an: Gossen Metrawatt GmbH Hotline Produktsupport Telefon D 0900 1 8602-00 A/CH +49 911 8602-0 Telefax +49 911 8602-709 E-Mail support@gossenmetrawatt.com...
  • Page 15 11. Eingeschränkte Garantie und Haftungsbeschränkung Durch ständige Qualitätskontrollen, modernste Elektronik und hochwertige Werkstoffe gewährlei- sten wir, dass dieser Prüfer für die Dauer von 3 Jahren frei von Material- und Fertigungsdefekten bleibt. Diese Gewährleistung gilt nicht für Batterien, unsachgemäße Handhabung, nicht bestimmungs- gemäße Verwendung, öffnen des Gehäuses, falsche Lagerung oder Schäden durch Unfälle.
  • Page 17 3-349-592-02 Operating Instructions 1/9.20 METRAVOLT VT 1500 Voltage-Continuity Tester Gossen Metrawatt GmbH Südwestpark 15 90449 Nürnberg, Germany Telefon +49 911 8602-111 Telefax +49 911 8602-777 E-Mail: info@gossenmetrawatt.com www.gossenmetrawatt.com...
  • Page 18 at the back at the back 1 Test electrodes 2 Flashlight 3 Red LED for hazardous voltage ≥ 50 V AC / 120 V DC + Phase test 4 Orange LEDs for rotating field left/right 5 Green LED „Ω“ for continuity 0 ... 999 kΩ 6 Display (LCD) 7 Button : for flashlight and function HOLD...
  • Page 19 1. Application The METRAVOLT VT 1500 is a two-pole voltage tester with digital display. It complies with DIN EN 61243-3 (VDE 0682 part 401). With the METRAVOLT VT 1500 you can determine the existence and the strength of voltages within a...
  • Page 20 Please observe the following safety precautions:  The voltages indicated on the METRAVOLT VT 1500 are rated voltages. The voltage tester may only be used in systems working within this rated voltage range.  Faultless indication of display values is only guaranteed between -15°C ...
  • Page 21 3. Putting into Operation 3.1 Battery The instrument is already supplied with batteries. The battery status is indicated by a battery symbol on the display (see section 7.1). 3.2 Preparation Remove the safety cap from the electrodes. Push the handle with the test tip L1 upwards and detach it from the display part.
  • Page 22 3.3 Testing of Display and Function (Self-Test) In accordance with EN 51010-1 voltage testers must be checked if they function correctly, briefly before and whenever possible after use, for determining the absence of voltage. Step 1 – Display Test The device must be switched off for the self-test. Press and hold button .
  • Page 23 4. Measuring and Testing 4.1 General Information The METRAVOLT VT 1500 switches on automatically when a voltage of at least 12 V is applied or switches automatically to voltage testing. Note: For voltages below 12 V, the device must be...
  • Page 24 Note: You can perform tests above the certified nominal voltage range in accordance with IEC 61243-3. The maximum display range is up to 1200 V AC / 1500 V DC. The additional load may only be operated up to 1200 V AC / DC. For load tests in the prohibited range you will get a warning „Load“...
  • Page 25 - Press both push buttons at the back - The capacitor will be discharged 4.5.4 Start-up Testing of Electricity Meters The METRAVOLT VT 1500 is suitable for performing start-up tests of digital electricity meters: - Test the voltage at the output side of the meter between phase and neutral conductor to this end.
  • Page 26 4.6 Testing of Phase and Phase Sequence Attention! These tests can only be performed at a nominal volt- age of at least 165 V (50 Hz) against earth. When performing these tests, the device must be gripped firmly at the handle of the display part. Note: You may wear insulating gloves when per- forming the tests.
  • Page 27 +L2. If a voltage of 12 V or more is applied in this operating mode, the device switches automatically to voltage testing. 5. Test Point Illumination The METRAVOLT VT 1500 is equipped with a test point illumination. Before measuring, press button to switch the light on or off.
  • Page 28 6. Technical data METRAVOLT VT 1500: Nominal voltage certified in accordance with range: IEC 61243-3 0 ... 1000 V AC / 1500 V DC Display range: 0.03 V ... 1500 V DC 0.15 V ... 1200 V AC Measurement range/ 0.10 V ... 19.99 V ±...
  • Page 29 Return is free of charge and required by law. 8. Maintenance / Storage 8.1 General Information The METRAVOLT VT 1500 is maintenance free. Nev- ertheless, observe the following details in order to ensure safe operation: Always keep the voltage tester dry and clean. The housing can be cleaned with a cloth dampened with isopropyl (alcohol) or soapy water.
  • Page 30 This address is only valid in Germany. Please contact our representatives or subsidiaries for service in other countries. 10. Product Support When you need service, please contact: Gossen Metrawatt GmbH Hotline Produktsupport Phone +49 911 8602-0 +49 911 8602-709 E-Mail support@gossenmetrawatt.com...
  • Page 31 11. Limited Warranty and Limitation of Liability By means of continuous quality checks and produc- tion controls, state-of-the-art electronics and high quality materials we guarantee that the tester will be free from defects in material and workmanship for a period of 3 years. This warranty does not cover batteries, damages resulting from improper handling, use for any other than the intended purpose, opening the housing,...
  • Page 33 3-447-085-02 1/9.20 Mode d’emploi METRAVOLT VT 1500 Détecteur de tension et de continuité Gossen Metrawatt GmbH Südwestpark 15 90449 Nürnberg, Allemagne Téléphone +49 911 8602-111 Télécopie +49 911 8602-777 Email : info@gossenmetrawatt.com www.gossenmetrawatt.com...
  • Page 34 au dos au dos 1 Pointes de touche 2 Éclairage des points de mesure 3 LED rouge pour tensions dangereuses ≥ 50 V CA / 120 V CC + contrôle de la phase 4 LED orange pour indiquer l’ordre des phases gauche/droite 5 LED verte « Ω » pour continuité de 0 à 999 kΩ 6 Écran (LCD) 7 Touche  : pour l’éclairage des points de...
  • Page 35 1. Application Le METRAVOLT VT 1500 est un détecteur de tension bipolaire à affichage numérique, conforme à DIN EN 61243-3 (VDE 0682 partie 401). Il vous permet de mesurer des tensions de 0 V à 1 000 V CA / 1 500 V CC à des fréquences pou- vant atteindre 2 kHz et de contrôler la phase, le sens du champ tournant et la continuité.
  • Page 36 Observez les mesures de sécurité suivantes :  Les indications de tension sur le METRAVOLT VT 1500 représentent des valeurs nominales. Vous ne devez l'utiliser que sur des équipements dont la tension nominale est située dans cette plage  L’affichage impeccable n’est garanti que dans la plage de température de - 15 °C à...
  • Page 37  Avant d’utiliser le détecteur, vérifiez le parfait état du boîtier et du cordon de mesure. Si des dommages sont visibles, le détecteur doit être mis hors service. Nettoyer le détecteur avant usage s’il est forte- ment sali.  Le détecteur de tension doit être stocké dans un local propre et sec.
  • Page 38 3.3 Contrôle de l’affichage et test de fonctionne- ment (test interne) Selon EN 50110 -1, il faut vérifier le parfait fonction- nement des détecteurs de tension juste avant de les utiliser et, si possible, également après l’utilisation pour contrôler l'absence de tension. Étape 1 - Test de l’affichage L’appareil doit être éteint pour le test interne.
  • Page 39 4. Mesures et tests 4.1 Remarques générales En présence d'une tension à partir de 12 V, le METRAVOLT VT 1500 s'allume automatiquement ou passe du mode « Test de continuité » au mode « Test de tension ». Remarque : pour les tensions inférieures à 12 V, il faut allumer l’appareil avec la touche...
  • Page 40 Remarque : vous pouvez fiablement exécuter des contrôles au-dessus de la plage de tension nominale certifiée selon CEI 61243-3. La plage d’affichage maximale est de 1 200 V CA / 1 500 V CC. La mise en circuit de la charge ne doit pas excéder dans ce cas 1 200 V CA / CC. Si des contrôles sous charge sont effectués dans une plage non autorisée, « Load »...
  • Page 41 - Appuyez sur les deux touches à l'arrière de l’appareil - Le condensateur se décharge 4.5.4 Contrôle du démarrage des compteurs Le METRAVOLT VT 1500 est en mesure de tester le démarrage des compteurs numériques sous l’effet de la charge mise en circuit : - Contrôlez dans ce cas la tension côté...
  • Page 42 4.6 Tests de la phase et de l’ordre de phases Attention ! Ces essais fonctionnent à partir d’une tension nomi- nale de 165 V (50 Hz) contre la terre. Lors de ces contrôles, l’appareil doit être tenu ferme- ment à la poignée de la partie afficheur. Remarque : des gants isolants peuvent être portés.
  • Page 43 5. Éclairage du point de mesure Le METRAVOLT VT 1500 possède un éclairage des points de mesure. Appuyez, avant la mesure, sur la touche pour activer ou désactiver la lumière.
  • Page 44 6. Caractéristique techniques METRAVOLT VT 1500 : Tension nominale : certifiée selon CEI 61243-3 0 à 1 000 V CA / 1 500 V CC Plage d’affichage : 0,03 V à 1 500 V CC 0,15 V à 1 200 V CA Plages de mesures/ 0,10 V à 19,99 V ± 1 % + 3 D Exactitude : 20,1 V à 99,9 V ± 1 % + 3 D 100 V à...
  • Page 45 Degré de pollution : Indice de protection : IP 65, peut être utilisé en cas de pluie Câble : cordon sous gaine PUR, 1 000 V, 1 m, avec capuchon de protection Normes : DIN EN 61243–3 VDE 0682- 401: 2015 2015- 08 CEI 61243-3:2014 + Cor.:2015 Essai de requalification / étalonnage : tous les 6 ans Dimensions/poids : 275 x 89 x 35 mm (éléments poignée et afficheur)
  • Page 46 8. Maintenance / stockage 8.1 Informations générales Le METRAVOLT VT 1500 ne nécessite aucune main- tenance. Il faut cependant veiller aux points suivants pour un fonctionnement en toute sécurité : Votre détecteur de tension doit rester sec et propre. Le boîtier en plastique peut être nettoyé avec un chiffon imbibé...
  • Page 47 11. Garantie restreinte et limitation de responsabilité Nous garantissons par des contrôles constants, une électronique ultra moderne et des matériaux de qualité que ce détecteur restera exempt de vices de matériaux et de fabrication pour une durée de 3 ans. Cette garantie ne s’étend pas aux piles, à...