3. Mounting

Mount the unit with two clamps in the control panel, cutout 91 x 43mm.

4. Electrical connection

Disconnect the installation. The plug-in terminal strip features reverse polarity
protection.
Connection:
The terminals 1 to 17 are electrically isolated
from the mains.
12
X1
1
GND
2
+24 V DC IN
3
GND
4
+5 V DC OUT
5
+ 24 V DC OUT
6
0 - 1V
7
0 - 10 V
8
0 - xx V
9
0/4-20 mA
10
n. c.
11
n. c.
12
n. c.
13
n. c.
14
OUT 1 (min.)
15
OUT 2 (max.)
16
OUT 3 (display 0)
17
+ 24 V Com
X2
L 230 V AC
L 115 V AC
N
DC supply
sensor supply
signal inputs
terminals must
not be used
outputs
AC supply