Minimum Clearance For Positioning The Air Intake; Flue Gas Exhaust Duct; Pipes And Maximum Usable Lengths - ZANTIA CINEA CANALIZÁVEL Manuel D'utilisation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Floor
fig. 7 floor protections
2.5.4
MINIMUM CLEARANCE FOR POSITIONING
THE AIR INTAKE
The combustion air intake of the pellet stove cannot be con-
nected to an air distribution system or to a wall air intake. The
described measures and requirements must be complied
with to ensure its correct and safe positioning. These distanc-
es must be observed to prevent taking combustion air from
another source; for example, opening a window can suck out
the outside air, depriving the stove of it.
The air intake must be located at least at:
1.5 m
1.5 m
0.3 m
1.5 m
tab.2 min. clearances air intake positioning
EN
12
Protection
min. 2 mm
beneath
Doors, windows, flue
Horizontally away
gas exhausts, gaps,
etc.
Above
Away from
Flue gas outlet
Air intake with
non-lockable
grille
translated from the original text
2.5.5

FLUE GAS EXHAUST DUCT

The pipes must ALWAYS be installed according to the
standards and instructions of the manufacturer and any-
way with the silicon gasket supplied to guarantee its seal-
ing.
IT is prohibited to install dampers or other valves that can
obstruct the flue gas exhaust.
IT is prohibited to install one flue in which flue gas or
vapours of other appliances (boilers, hoods, etc.) are ex-
hausted.
2.5.6

PIPES AND MAXIMUM USABLE LENGTHS

Pipes made of painted aluminised steel (minimum thickness
1.5 mm), stainless steel (Aisi 316) with a 100 mm diameter (for
pipes inside the flue max. 150 mm). Hoses (made of stainless
steel with smooth internal wall) can be used if they fall within
the limits set forth by law; the male-female coupling collars
must have a minimum length of 50 mm. The diameter of the
pipes depends on the type of system.
TYPE OF SYSTEM
Minimum length
Maximum length (with 3 90° elbows)
For installations located at over 1200 m asl
Maximum number of elbows
Horizontal segments with min slope 5%
tab.3 max. pipe length
NOTE: pressure drops of a 90° elbow can be com-
pared to those of 1 metre pipe; the inspectable tee
fitting must e considered as a 90° elbow.
Installation
WITH Ø 100 mm DOU-
BLE WALLED PIPE
2m
8m
mandatory
4
2m
Fitting
Tee fitting
rev 00
Mod. CINEA CANALIZÁVEL