Evolution Series Poke-Thru Devices are UL Listed and Classified to U.S. and Canadian safety standards
to the following conditions:
The 6STC Poke-Thru Stem with the 6CTC2 or 6CT2 Service Head Fitting, and the 6ATC2P, 6AT2P, 6ATC2PAV 6AT2PAV, 6ATC2 or
6AT factory assembled Poke-Thru devices are for use with 1-, 1 1/2 -, or 2- hour rated unprotected reinforced concrete floors and
1-, 1 1/2 -, or 2- hour rated floors employing unprotected steel floor units and concrete topping (D900 Series Designs), or concrete
floors with suspended ceilings. (Fire resistive designs with suspended ceilings should have provisions for accessibility in the ceiling
area below the Poke-Thru fittings).
The assembled Poke-Thru stem and service fitting will not reduce the ratings of the floor assembly when the thickness and type of
concrete (required for the specific rating) are within the specified limits and the fittings are installed as specified:
1. Spacing – Minimum of 2' (610mm) OC and not more than one unit per 65 sq. ft. (6 sq. m) of floor area in each span.
2. Concrete – Minimum thickness of structural concrete topping of 2 1/4" (57mm) over metal deck or a minimum 3" (76mm)
thick reinforced concrete slab. Unit weight of concrete to be 110 to 155 pcf.
3. Installation – Mounted in a 6" (152mm) diameter hole in concrete per installation instructions accompanying the fittings.
For use with power circuits, data and/or audio/visual cables as tabulated below:
COPPER CROSS-SECTION
Max Copper
X-Section
Max #
Conductors
NOTE:
When using conductor sizes other than listed above, the aggregate cross-sectional area of
the copper conductors shall not exceed the cross-sectional areas listed.
The "TC" suffix letters indicate that the device may be installed on tile or carpet covered concrete floors. The "T" suffix
letter indicates that the device is intended to be installed on a concrete floor, embedded into the tile covering.
Copper Cross Sectional Area
of Commonly Used Conductors
Size
#24
.00032 sq. in. (.20645mm2)
#22
.00050 sq. in. (.32258mm2)
#14
.00323 sq. in. (2.08386mm2)
#12
.00512 sq. in. (3.30321mm2)
#10
.00815 sq. in. (5.25805mm2)
#8
.01296 sq. in. (8.36127mm2)
NOTE: Use above values for solid or stranded conductors.
CAUTION: Receptacle supplied with this Poke-Thru is not suitable for direct field wiring.
Contact manufacturer for replacement. Field modifications will void UL Listing
and Classification. Replacement receptacle is limited to this manufacturers'
Catalog No 68REC.
OUTER
CHANNELS
.0154 sq. in.
.0387 sq. in.
(9.9mm2)
(24.97mm2)
(3) 12 AWG
(12) 14 AWG
Solid
CENTER
CHANNEL
13