▲ ▼ Alarm buzzer -OK-
The alarm buzzer can be switched on and off here.
▲ ▼ Button beep -OK-
The beep which sounds when a button is
pressed can be turned on or off here.
▲ ▼ Language -OK-
The arrow buttons can be used to switch to English, French,
Dutch, Swedish or Polish. Pressing -OK- confirms the selec-
tion.
▲ ▼ Frost shut-off -OK-
Factory default setting is -10°C. This value can be altered here,
to any value between -19°C and 0°C.
▲ ▼ Ventilator -OK-
SH: If the ambient temperature is too high, one ventila-
tor switches on automatically. With the SH3, two ventilators
switch on.
The factory default setting is 35°C. It can be changed here to
any value between 20 and 39°C.
▲ ▼ Oil level PPCS -OK-
Selection: normally closed or normally open contact.
▲ ▼ Station ID -OK-
This menu item displays the number of the station.

POSSIBLE ERROR MESSAGES

PSV overpress. The pump sump ventilation has shut down for
safety reasons because the pressure was more than 6 bar.
PPCS overpress. The pressure pipe ventilation has shut down
for safety reasons because the pressure was more than 6 bar.
Check whether the shut-off devices for the pressure pipe in
the chamber and for the flushing device are open.
Furthermore, there may be a blockage in the pressure pipe. In
this case, clear the obstruction.
SafStat40. The ambient temperature exceeded 40°C, and the
unit was shut down for safety reasons.
Frost. The ambient temperature has dropped below 0 °C.
Power failure. The power supply has failed.
M-I. Motor protection. The compressor motor protection
switch has tripped.
Date/Time. The date and time must be re-entered.
Communication. No response received from a module.