General description

2.1 3-way ball valve

2.1.1
Applications
The 3-way ball valves (1", 1¼", 1½" or 2" with Rp connection ac-
cording to ISO 7/1) are suitable for:
use as a flow temperature mixer in the heating circuit
other mixed applications
2.1.2
General installation instructions
Note:
Installation of the fitting in the pipework must be carried out
without mechanical stress.
The fitting must not be used as a fixed point; it is supported
by the pipework.
The fitting and the pipework must be free from dirt, welding
beads etc.
Fig. 2.1:
Installation recommendation for avoiding excessive flow noise in HVAC systems.
The installation of dirt traps (available as a special acces-
sory) is recommended in order to prevent water contamina-
tion caused by rust particles, welding beads etc.
All ball valves must only be used in closed circuits. An ex-
cessive oxygen mixture in open circuits can destroy the ball
valves.
To ensure that no disturbing flow noise can be heard in quiet
rooms, the pressure differential over the ball valve must not
exceed 50 % of the specified values.
www.dimplex.de
ATTENTION!
Please note that the heat pump manager (HPM) has a maximum of two
mixer outputs.
Switching is carried out by an EMA DWK electromotive actuator,
which is activated by the heat pump manager.
The pipework must be without pressure, the media must be
cooled down and the system must be emptied before the fit-
ting is removed.
The connections of the 3-way ball valve are fitted with a Rp
internal thread. Screw threads are to be sealed using mate-
rials suitable for this purpose.
The 3-way ball valve can be installed in different positions. If
the ball valve is activated by an actuator, upside down instal-
lation is not recommended (risk of condensate entry, drip-
ping water etc. along the valve spindle)!
The ball valves are not suitable for use in potentially explo-
sive atmospheres.
The individual materials used are approved for use in con-
nection with domestic water. The ball valves as complete
units are not approved for domestic hot water.
When glycol-water mixtures are used, it is recommended
that a maximum concentration of 50 % glycol should not be
exceeded.