Table 4. UPS Weights and Dimensions
IBM Model
B42 (3 kVA)
B43 (3 kVA)
B46 (6 kVA)
B47 (6 kVA)
4
UPS Weight
180 lb (81.9 kg)
180 lb (81.9 kg)
257 lb (116.8 kg)
257 lb (116.8 kg)
5. Allow 12" (30.5 cm) of clearance at the top and back and 6"
(15.2 cm) on the sides of the power and optional battery
enclosure for adequate airflow. Allow 36" (91.5 cm) in the front
of the enclosure to access the operator control panel and to
install and maintain battery and power modules (see Figure 2).
6"
Figure 2. Clearance Measurements (Front View)
Axxium
Pro 9910 Installation Guide for IBM Applications
t
Maximum Weight
420 lb (190.9 kg)
420 lb (190.9 kg)
377 lb (171.4 kg)
377 lb (171.4 kg)
12"
36"
Dimensions (HxWxD)
33.3" x 17.0" x 25.6"
(84.5 x 43.0 x 65.0 cm)
33.3" x 17.0" x 25.6"
(84.5 x 43.0 x 65.0 cm)
33.3" x 17.0" x 25.6"
(84.5 x 43.0 x 65.0 cm)
33.3" x 17.0" x 25.6"
(84.5 x 43.0 x 65.0 cm)