Trimod Besta Level Switch – types XI...8, XIE9...8
for use in potentially explosive atmospheres acc. to directive 2014/34/EU
Legend
Information: Application hints and important information. To be followed for optimal function.
Attention:
Requirements and prohibitions to prevent damages, especially to material and the environment.
Danger:
Dangerous situation that can lead to injury and death if instructions are not followed.
1.

Safety instructions

The operating manual must be read and understood before installation. If you are uncertain on any
point, please contact Bachofen AG, Switzerland.
The electrical connection may only be carried out by qualified personnel who have been authorised by
the operator.
All attached cables and cable bushings must comply with the requirements of EN 60079-0
Appendix A: explosion-proof cables and cable entries.
The supply voltage may only be applied after the cover has been closed. Please ensure that you
always observe the special regulations concerning work on explosion-proof devices and during work in
potentially explosive atmospheres at the operators site.
Every Trimod Besta level switch must be selected by qualified, trained personnel in accordance with
the specifications stipulated by the customer. These specifications must be kept by the operator in a
safe place, together with the operating manual, the customer-specific designation and the type
number (see type plate). In the event of any deviation of the physical quantities (pressure, tempera-
ture, density, etc.) from the original specification, the suitability of the level switch must be checked
again by qualified, trained personnel or by the manufacturer, with regard to the new specifications.
If the device is mounted in a partition wall, which separates zones from one another, and if category 1
or 2 equipment is necessary, an equipotential bond must be made (contact resistance ≤ MΩ) between
the metal housing of the level switch and the wall of the container.
The float and flange module must be included in the regular plant pressure tests.
Process vessels / float chambers must be brought to atmospheric pressure before work is carried out
and must be appropriately vented.
The devices may, under no circumstances, be used as a support aid or as a security fixture for
equipment structures or for persons.
When you are using a Trimod Besta level switch in a safety application according to
IEC 61508 and IEC 61511, the safety manual must be taken into consideration before
installing and commissioning the switch. The safety manual lists the restrictions and limitations of the
IEC 61508 certification of the Besta Trimod level switch. The safety manual can be downloaded from
http://www.trimodbesta.com/en/downloads/approvals/sil.html
2.

Conformity of standards

Trimod Besta level switches conform with the requirements of:
EN 60079-0, EN 60079-1, EN 60079-11, EN 60079-26
IEC 61508:2010 (Safety Integrity Level)
www.trimodbesta.com
Operating instruction – English
8 │ 24
LTB004X │ 2016.08