Télécharger Imprimer la page

LEGRAND Wattstopper BZ-150 Instructions D'installation page 2

Publicité

Les langues disponibles

Les langues disponibles

Single BZ-150 with one or more sensors
Neutral
White
BZ-150
Auto
ON
Line 120VAC
Black
Power Pack
277VAC
Cap
2-wire Push Button
Low Voltage
Momentary
Grey
Manual ON
Switch Option
Wiring
Red
24VDC
With the BZ-150, the load can be turned ON and OFF automatically using an occupancy sensor input, a timer, panel or BAS input, and
manually from an optional low voltage momentary switch. Use the Mode Switch to select either the Auto ON mode, or the Manual ON
mode. Remove power from the BZ-150 when changing the switch setting, or cycle power to it after changing the setting.
Auto ON (Mode Switch LEFT - default)
The occupancy sensor input, Hold ON input and the optional momentary switch input can all be used turn ON the load.
When the load is turned OFF using the momentary switch, the BZ-150 does not turn it ON automatically until after the sensor time delay
expires (e.g., as might be required for a presentation). Pressing the momentary switch before the sensor time delay expires turns ON
the load.
When the occupancy sensor's time delay expires, the BZ-150 reverts to Auto ON mode and it turns ON the load with the next input from
the occupancy sensor.
Manual ON (Mode Switch RIGHT)
Occupants must press the low voltage momentary switch to turn ON the load.
When the occupancy sensor is the only input keeping the load ON, the load turns OFF when the sensor's time delay expires. If the
sensor input re-triggers within 30 seconds after the load turns OFF, the load turns ON again. After 30 seconds expire with no sensor
input, press the momentary switch to turn ON the load.
Four +12-24VDC input wires are provided to control the load relay. The inputs may be used in combination or individually, depending on
the needs of the application. See the WIRING section for wiring information.
Maintained Inputs:
Control ON (Blue) – This input is intended for occupancy sensor input. Applying 12-24VDC closes the relay. Remove the voltage and
the relay opens if no other input is holding it closed.
Hold ON (Orange) – This input is intended for timer or panel input. Applying 12-24VDC closes the relay. Remove the voltage and the
relay opens if no other input is holding it closed. It overrides Control ON input.
Hold OFF (Brown) – This input is used for timer, panel, BAS or load shed input. Applying 12-24VDC opens the relay. Remove the
voltage and the relay can accept any other input. It overrides Control ON and Hold ON inputs.
Momentary Input:
Manual ON/OFF (Grey) – This input is for a low voltage momentary switch. Applying 12-24VDC momentary input changes the relay
to the opposite state. It overrides Control ON, Hold ON and Hold OFF inputs.
Optional
Local
Off
Switch
Red
Man
ON
Red
LVSW-101
Low Voltage
Switch Input
SW1
COM
Cap
Control Output
Any
24VDC
Common
Ceiling/Wall
Sensor
+24VDC
3-wire Momentary, DCC2
Grey
Manual ON
Install
Red
Jumper
24VDC
Wire
LOW VOLTAGE INPUTS
White
Neutral
Line 120VAC
Black
277VAC
Fixture
Class 2
Low Voltage
Wires
5-30 VDC In
Hold ON
Dry Contact
*To
Additional
5-30 VDC In
Sensor(s)
Hold OFF
Multi-button Switch, LVSW-101
Do not use pilot or locator
light connections
Grey
S(x)
Manual ON
Red
Com
24VDC
OPERATION
2
BZ-150 with Hold On or Hold Off
Red
BZ-150
Auto
Man
ON
ON
Red
Power Pack
Cap
Control Output
Common
+24VDC
Mode
Switch
Model #:
BZ-150 Power Pack
120/230/277VAC, 50/60Hz, 225mA output
APPLIANCE
20A ballast or incandescent load
CONTROL
88T9
Motor load: 1HP@120/240VAC
Class 2 power supply
White
Power Pack
Neut.
UL 2043 Plenum Rated
Black
120VAC
Hot
277VAC
Orange
Santa Clara, CA
+12-24VDC In
Hold ON
800.879.8585
Auto
Manual
+12-24VDC In
ON
ON
Hold OFF
Brown
Momentary Switch (optional)
Optional
Local
Off
Switch
Fixture
Any
*To
24VDC
Additional
Ceiling/Wall
Sensor(s)
Sensor
Low Voltage
Inputs
Red
Lighting
Load
Red
Low Voltage Wires
Control
Any 3-Wire
Common
24VDC
+24VDC
Sensor

Publicité

loading