Supplies Required:
• (3) 3/8" bolts and wall anchors for mounting
wall bracket
• Pipe sealant
• Piping to 1/2" IPS water supply inlet on unit
• Piping to 1-1/4" IPS drain outlet
• Sign-mounting hardware
Step 1: Install inlet drain fittings
NOTE: The top of the eyewash heads should
be 33"–45" (838mm–1143mm) from the floor.
1. Position the inlet drain fitting over the 1-
1/4" drain outlet pipe from wall.
2. Using the inlet drain fitting as a template,
mark the bolt hole locations on the wall
OR install three suitable fasteners
(supplied by installer) for 3/8" bolts in the
wall at the marked hole locations (see
Figure 1).
3. Bolt the inlet drain fitting to the wall or
wall fasteners using 3/8" bolts (supplied
by installer).
Step 2: Assemble eyewash
components
1. Assemble eyewash components as shown
in Figure 2a on page 4 or Figure 2b on
page 5.
• Apply pipe sealant (supplied by
installer) to all male-threaded pipe
joints.
• Use a strap wrench around pipes when
tightening to prevent marring.
Step 3: Connect water supply
1. Connect the water supply piping (supplied
by installer) to the 1/2" IPS inlet on the
eyewash.
2. Connect the tailpiece to the 1-1/4" IPS
drain outlet on the eyewash.
3. Mount the safety sign to the wall using
sign-mounting hardware (supplied by
installer).
4. Open the water supply lines. Test for leaks
and adequate water flow.
Bradley Corporation • 215-158FW Rev. J; EN 06-532E

S19-220FW

Wall
13-1/4"
(337mm)
Ø 10" (254mm)
15-1/2" (394mm)
8-1/8"
(206mm)
2-1/4"
(57mm)
7-1/2"
Ø 3/8"
(191mm)
(9mm)

S19-220T

Wall
(13-5/8")
346mm
Ø 10-3/4" (273mm)
15-7/8" (403mm)
8-1/8"
(206mm)
2-1/4"
(57mm)
7-1/2"
Ø 3/8"
(191mm)
(9mm)
Figure 1
4/20/07
S19-220FW, S19-220T
4-1/2"
(114mm)
8-1/4"
(210mm)
4"
(102mm)
36" (914mm)
Suggested
Height
To Floor
29-1/2"
(749mm)
Suggested
Height
To Floor
5-1/4"
(133mm)
4-1/2"
(114mm)
8-1/4"
(210mm)
4"
(102mm)
36" (914mm)
Suggested
To Floor
29-1/2"
(749mm)
Suggested
Height
To Floor
5-1/4"
(133mm)
Height
3