Note:
"1221" is the preset PIN for accessing the configuration menu.
Finally, press the "Return" key (fig. 11, item 8). The Config menu will appear.
Use the "Down" key or the "Up" key to select the "IP v4" entry.
Click the "Return" key to confirm your selection. The DHCP menu will appear.
Use the "Down" key or the "Up" key to select the "No" entry. This will now appear on a red back-
ground.
Click the "Return" key to confirm your selection. The IP v4 menu will appear.
In the same way as you entered the PIN, enter an IPv4 address permitted in the network for the "Ad-
dress" entry.
If necessary, correct the settings for the subnet mask and the gateway.
Click the "Return" key to confirm your entries. The Config menu will appear.
Finally, press the "Esc" key. The Main menu appears.
Connect the PDU to your Ethernet LAN with a network cable (fig. 11, item 5).
6.2
Settings via the PDU website
Using a network cable, connect the device to your computer via the Ethernet interface (fig. 11,
item 5).
Note:
You may need to use a cross-over cable for this purpose.
Change your computer's IP address to any address within the range 192.168.0.xxx, e.g.
192.168.0.191. The default address 192.168.0.200 of the device must not be used.
Set the subnet mask to the value 255.255.255.0.
If applicable, switch off the proxy server in the browser to facilitate a direct connection to the device.
In the browser, enter the address http://192.168.0.200 (fig. 13, item 1). The login dialog for logging
in to the device will be displayed.
Log in with the username admin and the password admin (fig. 13, item 2).
In the left-hand section of the overview window (navigation area), click the Processing Unit entry
(fig. 13, item 3), and in the right-hand section (configuration area), click the Configuration tab
(fig. 13, item 4).
In the Network group box, click on the TCP/IP button (fig. 13, item 5).
Note:
The following sections describe in detail how to make the setting for the IPv4 protocol.
Further notes regarding the TCP/IP configuration can be found in section 1.1.
In the TCP/IP Configuration window, change the device's IP address in the IPv4 Configuration
group box to an address permitted in the network (fig. 13, item 6).
If necessary, correct the settings for the subnet mask and the gateway.
Alternatively, select the "DHCPv4" setting instead of "Manual" for automatic IP allocation.
Click on the Save button to change your settings.
Change the network settings of your computer to its original values for the IP address and the subnet
mask.
Rittal PDU international/PDU UK power distribution unit
Settings of the PDU metered/switched/managed
EN
21