Settings of the PDU metered/switched/managed
5.2
Installation
Connect the PDU to a TN-S or IT network. Please note the detailed information in section 8 "Tech-
EN
nical specifications".
Depending on the PDU version, provide the following pre-fuse:
– PDU international: 3 x 16 A (3~/16 A versions), 3 x 32 A (3~/32 A versions), 1 x 16 A (1~/16 A ver-
sions) or 1 x 32 A (1~/32 A versions)
– PDU UK: 1 x 16 A (16 A versions) or 1 x 32 A (32 A versions)
Route the PDU connection cable out of the IT rack and connect it to the mains supply.
Immediately after connection, the green LED to indicate the power supply illuminates continually
(fig. 11, item 6). Around 10 seconds later, the green multi-LED for the status display illuminates con-
tinually (fig. 11, item 4). After a further 15 seconds, the Rittal logo will appear first on the display, fol-
lowed a further 15 seconds later by the Main menu. The LEDs of the CAN bus connection (fig. 11,
item 2) and the Ethernet interface (fig. 11, item 5) are flashing green or yellow.
The entire start process will be complete after around 40 seconds when the measured power values
are shown on the display.
Connect one connection cable from the Rittal accessories to a free slot on the PDU and the equip-
ment.
Note:
When connecting the equipment, please note the maximum load per PDU slot (C13:
10 A, C19: 16 A, UK version: 13 A).
Depending on the PDU version, unused slots can be closed using the C13/C19 covers from the ac-
cessories (fig. 9).
If installation was unsuccessful: see section 1.1.
6
Settings of the PDU metered/switched/managed
The PDU is activated as standard to automatically obtain an IPv4 address from a DHCP server in the
network. If there is no DHCP server available, the following basic configuration is preset:
IP address:
Netmask:
Gateway:
If the PDU cannot be incorporated into the network with these settings, the settings can be amended
via the display or the PDU website.
6.1
Settings via the display
If the display is switched off: Press any key. The Main menu appears.
Press the "Esc" key (fig. 11, item 10). The Pin input menu appears.
Keep pressing the "Up" key (rig. 11, item 11), until the required digit is displayed in the first position
of the PIN.
Press the "Next" key (fig. 11, item 7) to move to the second position of the PIN.
Once again, keep pressing the "Up" key until the required digit is displayed in the second position of
the PIN.
Move to the third and fourth positions of the PIN and set them in the same way.
20
192.168.0.200
255.255.255.0
0.0.0.0
Rittal PDU international/PDU UK power distribution unit