SamplexPower SEC-1250UL Mode D'emploi page 22

Masquer les pouces Voir aussi pour SEC-1250UL:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

seCtIOn 7 |
!
cAUtion!
PleASe enSURe tHAt PoSition S1- on And S2 - on iS neVeR Selected
SelectinG tHe tiMe FoR StAGe 2 - ABSoRPtion StAGe ("U
Stage 2 - Absorption Stage ("Uo" Phase) is controlled by an internal timer circuit. Time
of 4 hours or 8 hours can be selected with the help of a pair of switches S3 & S4 of the
set of 4 DIP Switches (5). Check with the battery manufacturer for the optimum setting.
The preset value is 4 Hrs. Select the times as follows:
time
4 hours*
8 hours
Disable
* factory preset in this position
!
cAUtion!
PleASe enSURe tHAt PoSition S3- on And S4 - on iS neVeR Selected
RedUction oF MAxiMUM cHARGinG cAPAcity to HAlF FoR SAFe
cHARGinG oF loWeR cAPAcity BAtteRieS - HAlF PoWeR Mode
Batteries should not be charged at very high currents to ensure long life. Unless ap-
proved by the manufacturer, the maximum charging current should be limited to
approximately C/10 (where C is the Ah capacity of the battery at 20 Hour Rate). Thus,
at the rated current capacities (50A for SEC- 1250UL and 25A for SEC-2425UL), the Ah
capacity of the battery that should be charged with the charger will be:
• 50A x 10 = 500 Ah for SEC-1250UL
• 25A x 10 = 250 Ah for SEC-2425UL
If battery with lower Ah capacity is charged at the full charging rate, the battery life is
likely to be reduced.
A provision has been made to reduce the maximum charging current to approximately
half: 25A +/- 1A for SEC-1250UL & 12.5A +/- 1A for SEC-2425UL. This mode is termed as
"Half Power Mode". This mode can be selected by pressing push switch marked "Half
Power Mode" (8). When selected, a Green LED marked "Half On" (5) will be lighted.
When "Half Power Mode" is selected, batteries with the following lower capacities can
be safely charged at C/10 charging rate:
• SEC-1250UL - 250 AH
• SEC-2425UL - 125 AH
22 | SAMLEX AMERICA INC.
Preparing the Charger for Operation
diP Switch S3
off*
ON
off
diP Switch S4
ON*
off
off
" Phase)
0
type of Battery
Flooded / Wet Cell
Gel Cell & AGM
-

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Sec-2425ul

Table des Matières