Carrier 39CQ Instructions D'installation, De Fonctionnement Et D'entretien page 24

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Par
Description
1
Minimum speed (Hz)
2
Maximum speed (Hz)
3
Acceleration ramp-up (s / 100 Hz)
4
Deceleration ramp-down (s / 100 Hz)
5
Inverter configuration
6
Nominal motor current (A)
7
Nominal speed (rpm)
8
Nominal motor voltage (V)
9
Motor output factor (cos φ)
10
Access to the parameters
11
On/Off logic selection
12
Validation of the brake control
13
Not used
14
Not used
15
Pulse mode reference (Hz)
16
Analogue input mode 1 (mA)
17
Validation of negative preset speeds
18
Preset speed 1 (Hz)
19
Preset speed 2 (Hz)
20
Preset speed 3 (Hz)
21
Preset speed 4 (Hz)
22
Load display unit
23
Speed display unit
24
User scale setting
25
User security code
26
Not used
27
Keypad reference when powering on
28
Copying parameters
29
Loading of default settings
30
Selection of soft start mode
31
Selection of stop mode
32
Dynamic U/f selection
33
Flying restart selection
34
Mode selection (terminal B7)
35
Logic output control (terminal B3)
36
Analogue output control (terminal B1)
37
Maximum switching frequency (kHz)
38
Auto calibration
39
Nominal motor frequency (Hz)
40
Number of motor poles
41
Voltage mode selection
42
Voltage boost at low frequency (%)
43
Transmission speed by serial link
44
Serial link address
45
Software version
46
Brake opening current threshold (%)
47
Brake opening current threshold (%)
48
Brake opening frequency (Hz)
49
Brake closing frequency (Hz)
50
Time delay before brake opening (s)
51
Brake opening time delay (s)
52
Fieldbus node address
53
Fieldbus transmission speed
54
Fieldbus diagnostics
55
Last switch to safety mode
Factory setting
Setting 1:
Speed from
Eur
potentiometer
Level 1 parameters
0
50
0.55 kW motor: 97 , 1.1 kW motor: 60 , 1.4 kW motor: 65
5
10
AI.AV
AI.AV
Inverter rating
230 V /  :
400 V / Y:
1500
0.55 kW motor: 1390; 1.1 kW motor: 2880; 1.4 kW motor: 2839
230/400
230/400
0.85
0.55 kW motor: 0.8; 1.1 kW motor: 0.81; 1.4 kW motor: 0.88
L1
Level 2 parameters
0
diS
1.5
4-.20
OFF
0
0
0
0
Ld
Fr
1
0
3-digit code
0
no
no
1
1
OFF
0
dig
n=0
Fr
12-18
0
50
Auto
Ur l
3
19.2
1
50
10
1
2
1
1
0
0
0
0
EN - 8
Setting 2:
Speed from
contact
20
5
10
Pr
1 motor: 0.55 kW: 2.4; 1.1 kW: 4.2; 1.4 kW: 5
2 motors: 0.55 kW: 4.8; 1.1 kW: 8.4; 1.4 kW: 10
1 motor: 0.55 kW: 1.4; 1.1 kW: 2.4; 1.4 kW: 2.9
2 motors: 0.55 kW: 2.8; 1.1 kW: 4.8; 1.4 kW: 5.8
230/400
L2
0
diS
1.5
Volt
4-.20
OFF
Speed 1
Speed 2
Speed 3
Speed 4
A
A
Fr
Fr
1
1
3-digit code
0
Last
No
No
1
0
ON
2
Dig
n=0
Fr
12 - 18 (max)
0
50
Auto
Ur I
3
19.2
1
50
10
1
2
1
1
0
0
0
0
Setting 3:
Speed on the
keypad
Pad
230/400
4-.20
A
Fr
1
3-digit code
0

Publicité

Table des Matières
loading