Electrical installation

Warnings
Before connecting the appliance make sure that
the voltage is the same as indicated on the device
and the line supply is corresponding to the effective
rules.
The installation should always be carried out by a qualified
electrician or a competent person in accordance with the
current electrical standards for your country:
(ex. HD 384 CENELEC for Mainland Europe, IEC 60446 and BS
7671 for the United Kingdom, IEC 60445(2010) & ET101:2008
for Ireland and IEC 60364-7 1988 Internationally, AS/NZS 3000
for Australia) and according to the UE 2015/1188 standards.
The energy supply to the heater must always be properly
earthed.
The appliance must be connected to energy supply line by
means of the provided H05SS-F silicone cable.
An overvoltage category III Combined Circuit breaker and
Residual Current Device (RCD) with rated earth leakage
operation not exceeding 30mA must be fitted upstream on
the supply line in order to have a contact separation in all
poles that provide a full disconnection. The circuit breaker
must have a contact opening distance of at least 3 mm.
The product is in class I and IP55, wich is the protection rate
forthe units to be used even outdoor. For keeping the protection
rate of the appliance, the connection of the appliance with the
power supply must be done by means of a minimum IP55
system, as per the standards HD 384 CENELEC for Europe,
or international IEC 60364-7 1988.