Residual Hazards - Lenze ECSZZ020X4B Instructions De Montage

Filtre antiparasite
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Residual hazards

{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
Death or severe injuries when touching the power terminals.
ƒ
Protective measures:
Switch off the power supply and wait for at least three minutes before
ƒ
working on the power terminals.
Make sure that all power terminals are deenergised.
ƒ
{
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
Death or severe injuries when the device is touched in the event of a fault.
ƒ
Protective measures:
Implement the actions required in the EN 61800−5−1. Especially:
ƒ
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
³ 10 mm
EDKCSZZ040 DE/EN/FR 3.1
2
or PE conductor must be connected twice)
l
Safety instructions
Residual hazards
2
31

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Ecszz040x4b

Table des Matières