4.1.2.3 Operating LS mode with CBr master
The assignment value for the supply constant airflow is a function of a 0-10V signal connected to terminals K2 and
GND of the CBr. The link between voltage and airflow is linear. The exhaust constant airflow is equal to %EXT/PUL
of the supply airflow. (Except if 2 separate 0-10V signals are used to determine exhaust and supply constant
airflows, see advanced setup).
Starting/stopping the fans is carried out with entry K1 on the CBr. The K3 entry of the CBr can be used to activate
the pre-set multiplier (% on K3).
Wiring diagrams
To locate CBr module see section 3.1
a) Wiring diagram with 1 CBr module
b) Wiring diagram with several CBr in parallel
(*)
K1 closed
soft start
K1 open
softstop
K2
0-10V signal, maximum impedance allowed: 1500
K1+K3 closed
% on K3 activated
K3 open
% on K3 inactive
Caution: use goldplated contacts only
(*)