4.1.2 LS Mode : setup, operating instructions and wiring diagrams
4.1.2.1 Setup LS mode
The setup is made by means of the LCD screen and the 4 knobs SETUP, ↑, ↓ and ENTER of the RC.
To start the setup:
- Enter in the setup mode using the left knob on the diagram so that the SETUP LED ignites
- Press then the SETUP knob until the text 'SETUP' appears on the screen.
The idea is to select your choice with the ↑ ↓ knobs and then to confirm your choice by
pressing 'ENTER'. The numbers are introduced digit by digit.
1
LANGUAGE
Choose your language (English, French, Dutch, German)
WORKING
Select LS from CA, LS, CPs
2
MODE
3
V min?
Select minimum voltage value
4
V max?
Select maximum voltage value
5
m³/h≡Vmin
Select constant airflow value for minimum voltage Vmin
6
m³/h≡Vmax
Select constant airflow value for maximum voltage Vmax
Select constant airflow multiplier when contact between terminals +12V and K3 is
7
% on K3?
closed, or if position III is activated on the RC.
Type in ratio between exhaust (EXT) and supply (PUL) airflow to create over, under or
8
%EXH/SUP
even pressure.
PRESSURE
The pressure alarm is optional. If you do not wish it select N and skip to step15.
9
ALARM?
Otherwise select Y. For more details see §4.7.
∆P SUP
10
Type in the pressure increment for the supply airflow.
11
∆P EXH
Type in the pressure increment for the exhaust airflow.
INIT Pa
Do you wish to (re-)configure the reference pressure for the supply and the exhaust
12
REF?
airflows ? Y or N. (this is optional if it has been done previously)
If Y is selected, enter nominal airflow at which you wish to initialize the reference
13
m³h INIT
pressure. (same airflow for exhaust and supply air)
Pa REF
Initializing the reference pressure...
INIT
After +/-1 minute, the system will memorize the calculated pressure value of the fan as
the reference pressure. While initializing the airflow and pressure on F1 is displayed.
14
xxxx m³h
xxxx Pa
ALARM
Possibility to reset of the alarms. Y or N ?
15
RESET?
16
END SETUP
End