2. With the remote control off, press the FAN button for 10 seconds. When you have heard 3
«beeps», by holding the FAN button press at the same time the ON/OFF button. The counter
is already reset.
To exit from the confi guration menu press the ON/OFF button of the console.

11. ANTI-FROST MANAGEMENT

Termo-Reg unit has a function preventing ice formation in the recovery unit which is activated when
the temperature of exhaust air drops down to 1ºC, in which case the procedure is as follows:
• First, open the By-pass to prevent condensation in the recovery unit, thereby preventing the forma-
tion of frost.
• The equipment continue to run for several minutes to be monitored continuosly the exhaust air
temperature. If this does not rise by 1ºC, the equipment will stop.
• After 15 minutes stopped, the equipment will automatically start up, cyclically repeating the above
steps.

12. ALARMS

When an error occurs, the Termo-Reg unit informs to the user with the status LED control terminal
equipment
and by activating an available digital contact available in the electrical panel (Poten-
tial free). This LED fl ashes regularly during normal operation.
To know the error that is produced it is necessary to observe the LED the remote terminal status. In
case of failure, it emits a certain number of fl ashes depending on the error, as shown in the following
table:
Number of fl ashes
1
2
3
4
5
6
Error
Temperature sensor outside air
(ODA)
Temperature sensor supply air
(SUP)
Temperature sensor extract air
(ETA
Temperature sensor exhaust air
(EHA)
Temperature sensor water coil
Error battery
54
Description
Temperature sensor error outside air
(ODA)
Temperature sensor error supply air
(SUP)
Temperature sensor error extract air
(ETA)
Temperature sensor error exhaust air
(EHA)
Temperature sensor error water coil
(DC models)
DC models: water temperature = 10ºC.
Models DI: overheating