CHECKING THE QUANTITY OF GAS AT IGNITION
To check the quantity of gas at ignition, apply the following formula:
Ts x Qs ≤ 100
where Ts = Safety time in seconds.
Qs = Energy freed in safety time expressed in kW.
The Qs value is obtained from:
where Q1 = delivery expressed in liters freed in no. 10 startups in safety time.
Ts1 = total safety time of 10 startups.
Qn = Rated output
To obtain Q1 proceed as follows:
- Detach the lead from the control electrode (ionization electrode).
- Read the gas meter before the test.
- Perform 10 burner startups; these correspond to 10 safety lock-outs. Read the gas meter
again; by subtracting the first reading, the Q1 value is obtained.
Example: First reading
Final reading
total Q1
- By performing these operations, we can find Ts1 by timing no. 1 startup (safety lock-outs)
by the no. of startups.
Example: Actual safety time
- If, at the end of this checkup, the value is above 100, regulate the opening speed of the
main valve.
UK
00006,682 liters
00006,947 liters
00000,265 liters
= 1"95
Ts1
= 1"95 x 10 = 19"5