Mounting - Daikin EKSRDS2A Manuel D'utilisation

Solaire station de pression
Masquer les pouces Voir aussi pour EKSRDS2A:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 52

6.1 Mounting

X X
During heating up, liquid must be able to escape via the
discharge line of the safety valve (no obstructions).
Install the safety valve in such a way that it cannot be
shut off.
Do not install shut-off valves, filters or similar equipment.
X
Install the solar pump assembly in such a way that no ex-
ternal forces can act on the components after it has been
installed.
X
Do not overheat the components by welding or soldering
work performed on the system. Install the solar pump as-
sembly after completion of such welding or soldering
work.
X
Thoroughly flush the pipes prior to installing the solar
pump assembly. Impurities such as weld beads, hemp or
metal chips cause leaks of the safety valve and the check
valves.
X
Verify that the nominal pressure of the solar pump as-
sembly corresponds to the specification value of the sys-
tem.
X
Verify that the liquid in the system and the application ar-
ea of the solar pump assembly are compatible.
;
Sealing surfaces have been check for cleanliness and
damage.
;
All pipe ends are perpendicular and have been deburred.
is delivered ready to be installed. Do not dis-
assemble parts.
Remove the upper insulation.
1.
Hold
2.
(align with a level) and mark two positions.
Mounting and commissioning
with the lower insulation to the wall
13

Publicité

Table des Matières
loading

Table des Matières