9. Duct work

Use the recommended data to design the installation, so as to achieve best
silent performance.
Use non-combustible duct components.
Install sufficient thermal insulation to prevent condensation forming on outlet
duct flanges and outlet ducts.
Caution:
The noise from the intake will increase dramatically if intake A A A A A is fitted
directly beneath the main body. Intake A A A A A should therefore be installed as
far away from the main body as possible.
Particular care is required when using it with bottom inlet specifications.
To connect the air conditioner main body and the duct for potential equali-
zation.
[Fig. 9.0.1] (P.3)
A Air inlet
C Access door
E Duct
G Air filter
Caution for dew condensation-proof ducting
1. Use glass-wool duct (aluminum surface) as outlet duct in the field.
2. If use aluminum tape to fix the connection, be sure to proceed dew condensa-
tion prevention above the tape.

10. Electrical wiring

Precautions on electrical wiring
Warning:
Electrical work should be done by qualified electrical engineers in accord-
ance with "Engineering Standards For Electrical Installation" and supplied
installation manuals. Special circuits should also be used. If the power cir-
cuit lacks capacity or has an installation failure, it may cause a risk of elec-
tric shock or fire.
1. Be sure to take power from the special branch circuit.
2. Be sure to install an earth leakage breaker to the power.
3. Install the unit to prevent that any of the control circuit cables (remote control-
ler, transmission cables) is brought in direct contact with the power cable out-
side the unit.
4. Ensure that there is no slack on all wire connections.
Transmission cable specifications
Type of cable
Cable diameter
Maximum length of transmission lines for centralized
control and indoor/outdoor transmission lines (Maximum
length via indoor units): 500 m MAX
Remarks
The maximum length of the wiring between power
supply unit for transmission lines (on the transmission
lines for centralized control) and each outdoor unit and
*1 Connected with simple remote controller.

10.1. Power supply wiring

Power supply cords of appliances shall not be lighter than design 245 IEC 57
or 227 IEC 57.
A switch with at least 3 mm contact separation in each pole shall be provided
by the Air conditioner installation.
Power cable size: more than 1.5 mm
[Fig. 10.1.1] (P.4)
A Switch 16 A
C Indoor unit
D Total operating current be less than 16 A
E Pull box
10
B Air outlet
D Ceiling surface
F Duct box
H Inlet grille
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
2
More than 1.25 mm
Max length: 200 m
system controller is 200 m.
2
B Overcurrent protection 16 A
3. There is possibility of dew condensation on the surface of aluminum tape or
glass-wool duct, which may develop to water-drop.
4. Dew condensation proof material recommendation: Polyethylene foam or
equivalent.
Thickness:
=
5mm: Wideness:
Isolated foamed (non-water-absorbing)
Heat conductivity:
0.032 W/(m·K)
=
The material should be applied to the duct around the outlet connection as shown
below.
[Fig. 9.0.2] (P.3)
A Aluminum tape
B Glass-wool duct
C Dew condensation proof material
D Indoor unit body
5. Some cables (power, remote controller, transmission cables) above the ceiling
may be bitten by mouses. Use as many metal pipes as possible to insert the
cables into them for protection.
6. Never connect the power cable to leads for the transmission cables. Otherwise
the cables would be broken.
7. Be sure to connect control cables to the indoor unit, remote controller, and the
outdoor unit.
8. Put the unit to the ground on the outdoor unit side.
9. Select control cables from the conditions given in page 10 .
Caution:
Be sure to put the unit to the ground on the outdoor unit side. Do not con-
nect the earth cable to any gas pipe, water pipe, lightening rod, or telephone
earth cable. Incomplete grounding may cause a risk of electric shock.
ME Remote controller cables
Sheathed 2-core cable (unshielded) CVV
2
2
0.3 ~ 1.25 mm
(0.75 ~ 1.25 mm
)*1
When 10 m is exceeded, use cables
with the same specification as
transmission cables.
CVVS, MVVS : PVC insulated PVC jacketed shielded control cable
CPEVS : PE insulated PVC jacketed shielded communication cable
CVV : PVC insulated PVC sheathed control cable
[Selecting non-fuse breaker (NF) or earth leakage breaker (NV)]
To select NF or NV instead of a combination of Class B fuse with switch, use the
following:
In the case of Class B fuse rated 15 A or 20 A,
NF model name (MITSUBISHI): NF30-CS (15 A) (20 A)
NV model name (MITSUBISHI): NV30-CA (15 A) (20 A)
Use an earth leakage breaker with a sensitivity of less than 30 mA 0.1 s.
Caution:
Do not use anything other than the correct capacity breaker and fuse. Using
fuse, wire or copper wire with too large capacity may cause a risk of mal-
function or fire.
=
150mm
MA Remote controller cables
2
0.3 ~ 1.25 mm
(0.75 ~ 1.25 mm
Max length: 200 m
2
)*1